Electrical connection

For devices of series MVT 600-

1050 DC, an electrical supply

must be laid as mains supply to

the outdoor unit as well as the

supplied 4-core control line from

the indoor unit to the outdoor

unit.

We recommend that screened

control lines are used with

a minimum cross-section of

1.5 mm².

Connecting the outdoor unit

Before making the connection,
observe the following information:

Customers should install
a terminal box in the vicinity of
the outdoor unit.

We recommend that a main/
repair switch is used (Figure 9).

Voltage is supplied to the
indoor unit through the
connection cable between
the outdoor component and
outdoor unit.

Details concerning the electrical
protection of the system are
given in the technical data.
Observe the required
diameters!

If the outdoor unit is installed
on a roof, ensure it is protected
against lightning strikes.

Label the electrical control lines
and the associated refrigerant
pipes of each interior device
with the same letter (A to D).

9 Connecting the outdoor unit

A vacuum of min. 20 mbar
must be created!

CAUTION

The time required to generate
the vacuum is dependent on
the pipework volume of the
indoor unit and the length of the
refrigerant pipes. This always takes
at least 60 minutes.

Once any foreign gases and
humidity have been completely
extracted from the system, the
valves on the pressure gauge
station are closed and the valves
on the outdoor unit are opened
as described in the chapter on
"Commissioning".

All electrical installation
work should be performed
by specialist contractors.
Isolate the voltage supply
when connecting the electrical
terminals.

CAUTION

10 Connecting the cable

Strain relief

Plug control

line indoor

unit A
Plug control

line indoor

unit C
Plug control

line indoor

unit B

Terminal block

Mains cable

Only connect the lines to their
associated connections as
labelled with the same letter.
Mixing up the assignment
of control lines and
refrigeration pipes can lead
to fatal consequences such as
compressor damage!

Proceed as follows to connect the
cable:

1. Remove the side panel next to

the terminals.

2. Select the cable cross-section

according to the relevant
standards.

3. Feed the cables through the

edge protection rings on the
fixed connection panel.

4. Insert the control lines into

the corresponding sockets. In
doing so, pay attention to the
alignment of the circuits.

5. If the supplied control lines

are too short, they can be
unclamped from the indoor unit
and extended by an electrician.

6. Support the cable in the strain

relief and re-assemble the unit.

Check all plugged and clamped
terminals to verify they are
seated correctly and making
a permanent contact. Re-tight-
en as required.

CAUTION

Additional sensor and control
lines may be required on some
indoor units.

NOTE

REMKO MVT

16