beautypg.com

REMKO MVT 600 DC User Manual

Page 11

background image

Display

Cause

Required action

E0

EEPROM error

Switch off the power to device for 1 min.

Contact specialist dealer

E1

Sensor suction pipe circuit 1 faulty / connection interrupted

Check the resistance of the sensor

( at 20°C=12.6k

Ω / 30°C=7.9kΩ)

E2

Sensor suction pipe circuit 2 faulty / connection interrupted

Check the resistance of the sensor

( at 20°C=12.6k

Ω / 30°C=7.9kΩ)

E3

Sensor suction pipe circuit 3 faulty / connection interrupted

Check the resistance of the sensor

( at 20°C=12.6k

Ω / 30°C=7.9kΩ)

E4

Sensor discharge liquefier faulty / connection interrupted

Check the resistance of the sensor

( at 20°C=12.6k

Ω / 30°C=7.9kΩ)

E5

Compressor voltage monitoring has tripped

Switch off the power to device for 1 min

E6

Sensor suction pipe circuit 4 faulty / connection interrupted

Check the resistance of the sensor

( at 20°C=12.6k

Ω / 30°C=7.9kΩ)

E7

Communication error between outdoor and indoor unit

Contact specialist dealer

P0

Excessive temperature (Klixon) compressor

Check refrigerant

Check the resistance of the compressor

sensor (normal 0

Ω)

P1

High pressure sensor has responded

Check refrigerant filling level,

check liquefier for soiling,

check fan AT

P2

Low pressure sensor has responded

Check stop valve AT, check refrigerant,

check electronic expansion valves,

P3

Overcurrent compressor has responded

Check winding resistance of the

compressor (1

Ω = U-V / U-W / V-W)

P4

LED AT

flashes 9 times

Rotational speed monitoring on compressor has responded

Check compressor connections and PCB

P4

LED AT

flashes 13 times

Rotational speed monitoring on compressor (inverter module)

has responded

Check connections CN4, CN1 on the AT PCB

Contact specialist dealer

P5

Excess temperature sensor on outdoor unit unit has responded Exterior temperature > 1h under -15°C

P6

Sensor outlet liquefier has responded

(Condensation temperature over 65°C)

Clean liquefier

Reduce air inlet temperature

Problem display by blinker code

11