The unit has been manufactured using state-of-the-art production methods and tested several times to ensure its
correct function. If malfunctions should occur, please check the unit as detailed in the list below. For installations
with an indoor unit and outdoor unit, refer to the chapter "Troubleshooting and customer service" in both
manuals. Please inform your dealer if the unit is still not working correctly after all the functional checks have been
performed!

Troubleshooting and customer service

Malfunction

The unit is running
with reduced or no
cooling output.

Exchange refrigerant lines

Are the injection pipes and

suction pipes of circuits A, B and

C correspondingly connected?

Check by a specialist

Exchange the electrical control
cable

Are the control pipes and

refrigerant pipes of circuits

A, B and C correspondingly

connected?

Check by a specialist

Air inlet and/or air outlet are
blocked by debris.

Debris in air inlet and air outlet
area?

Clean the fins.
Reduce the air resistance.

Thermal or wind load
was increased.

Have there been any
constructional / application-
related changes?

Reduce the thermal/wind loads
by implementing appropriate
measures.

No heat output possible.

Is the fan on the outdoor unit
running?

Fan / winter controller should be
checked.

Leaking refrigerant circuit

Are there signs of severe frost
on the large stop valve?

Repair by a specialist.

Fault

Possible cause

Check

Remedial measures

The unit does not start
or switches itself off.

Power outage, undervoltage

Are all electrical installations
functioning correctly?

Check voltage if necessary wait
before switching back on

Defective mains fuse
Main circuit breaker is open

Are all lighting circuits
functioning correctly?

Replace mains fuse
Close main circuit breaker

Damaged mains cable

Are all electrical installations
functioning correctly?

Repair by a specialist

Waiting time after switch-on too
short

Is there a restart after approx. 5
minutes?

Schedule longer waiting periods

Temperature outside operating
range

Are the fans in the unit still
working?

Observe the temperature ranges

Occasional overvoltage or
undervoltage

Check by a specialist

Turn the equipment off and back
on

Switch-off contact in external
condensation pump has opened

Is the external condensation
pump on the indoor unit
"faulty”?

Clean the condensation pump
drain
Have the pump replaced

The suction pipe and /
or liquid separator on
the compressor have
iced up

Thermal load has increased

Is the outdoor unit running
continuously?

Reduce the thermal load If
necessary, install an additional
device / insulate iced up
components

REMKO MVT

10