In automatic mode, the regulation autonomously selects between heating
and cooling operation, when the unit is first turned on. A nominal
temperature of 24 °C is preset. The regulating range is between 22 °C
and 26 °C. It can be increased or decreased by 1 °C with buttons /.
The fan speed cannot be changed.
AUTOMATIK
mode
AUTOMATIC
MODE
In cooling mode, the air in the room is cooled down to the adjusted
nominal temperature. The desired room temperature is set with buttons
/ in 1 °C increments. If the room temperature is 1 °C above the
selected nominal temperature, then the interior unit starts to cool down
the air in the room. If the adjusted room temperature is lower than
approx. 0.5 °C, then the regulation turns the cooling function off. To
protect the compressor, the regulation only turns the cooling on again
after a waiting period of 3 minutes.
COOLING
mode
COOLING
OPERATION
MODE
In the air circulation mode, the air in the room is only circulated.
The room temperature cannot be changed in this mode.
The cooling or heating operation is not activated.
AIR CIRCULATION MODE
AIR CIRCULATION
MODE
In the heating mode, you can heat the room in spring or fall. The desired
room temperature is set with buttons / in 1 °C increments. If the
room temperature is 1 °C below the selected nominal temperature, then
the interior unit starts to warm up the air in the room. If the adjusted
room temperature is exceeded by approx. 0.5 °C, then the regulation
turns the heater function off. To protect the compressor, the regulation
only turns the heater on again after a waiting period of 3 minutes.
H
EATING mode
HEATING
OPERATION
MODE