Installation – REMKO ATY 260 User Manual

Page 21

background image

Connection variations of
inner unit

Unit installation

When attaching the interior unit,
pay attention to the lower, upper
and side area air discharge.

1. Mark the mounting points on

the statically admissible building
sections, according to the
dimensions of the unit.

2. Open the display cover (Fig.

8)

and remove the two screws

underneath the filter (Fig. 9).

3. Remove the front of the unit

by lifting the front in the lower
area from the body approx. 10
cm and folding it upward
(Fig. 10)

.

4. Pull the plugs of the front cover

from the circuit board (Fig. 11).

5. If necessary, remove the break

out opening of the housing.

6. Install the unit on the wall.

7. Connect the refrigerant,

electrical and condensation line
to the interior unit, as described
below.

8. Recheck the horizontal

alignment of the unit.

9. Reassemble the unit.

Installation of the interior unit

The wall bracket for the unit must
be attached with suitable screws
and anchors.

Installation

The installation may only
be made by authorized
technicians.

NOTE

Oil return measures

If the exterior unit is located at a
higher level than the interior unit,
then suitable oil return measures
must be made. This is usually done
by fabricating an oil lift fitting,
which is to be installed for each
2.5 ascending meter.

Oil return measures

Exterior unit

Oil lift fitting in the

suction line to the

exterior unit

1 x for each 2.5

ascending meter

Radius:

50 mm

max. 5 m

exterior unit

8

Open display cover

4

Connection variations

1 Outlet on the wall, right
2 Outlet through the wall, right
3 Outlet through the wall, left
4 Outlet on the wall, left

View from the rear

1

2

9

Remove screws

10

Release the unit front

11

Pull off the plug

3

21