Remko aty, Troubleshooting and customer service, Functional problem – REMKO ATY 260 User Manual

Page 16

background image

Troubleshooting and Customer service

The units and components are manufactured with the most up-do-date manufacturing methods and are checked
several times for proper function. However, should a functional problems occur, please check the function
according to the chart below. When all functional checks have been completed and the unit still does not work
properly, please contact your dealer!

Problem

Possible cause

Check

Remedy

The unit does not start or does
not turn off by itself.

Power failure, low voltage, main

fuse defective / main switch

turned off.

Are all other electrical devices

working?

Check voltage, possible wait until

turned on again.

Power line damaged.

Are all other electrical devices

working?

Repair by certified service center.

Waiting time after turn on too

short.

Have 5 minutes passed after

restart?

Plan for longer waiting period.

Operating temperature fallen

below / exceeded.

Do the fans on interior unit and

exterior unit work?

Observe temperature ranges of

interior unit and exterior unit.

Power surge due to thunderstorm. Were there any lightning strikes

nearby lately?

Shut off main fuse and turn on

again.

Inspection by certified service

center.

Problem of external condensation

pump.

Did the pump turn off due to a

problem?

Check or clean the pump, if

necessary.

The unit does not react to
remote control.

Transmission distance too large /

receiving problem.

Is there a signal sound on the

interior unit when pressing the

button?

Reduce the distance to less than

6 m and change location.

Remote control is defective.

Is the unit working in manual

operation?

Replace remote control.

Receiver and transmitter are

exposed to too much sun

exposure.

Is it working in shade?

Shade the transmitter and receiver.

Electromagnetic fields disrupt the

transmission.

Is it working after turning any

possible interfering sources off?

No signal transfer at simultaneous

operation of interfering sources.

Button of remote control stuck /

dual button control.

Does the “Send” symbol appear in

the display?

Release the button / press only

one button.

Batteries of remote control are

discharged.

Have new batteries been inserted?

Is the display incomplete?

Insert new batteries.

The unit works at reduced or
no cooling output.

Filter is dirty / air inlet / outlet

opening is blocked by debris.

Have the filters been cleaned?

Clean filters.

Windows and doors are open.

Heating or cooling load has

increased.

Have there been any

constructional / user changes?

Close windows and doors / install

additional systems.

No cooling operation is set.

Is the cooling symbol in the

display activated?

Correct the adjustment of the unit.

Fins of the exterior unit are

blocked by foreign matter.

Does the fan of the exterior unit

work? Are the evaporator fins

clear?

Check fan or winter regulation,

reduce air resistance.

Leaks in refrigerant circuit.

Is frost formation visible on

connections of the exterior unit?

Repair by certified service center.

Condensation discharge on unit.

Drain pipe of collector reservoir

plugged / damaged.

Is unrestricted condensation

discharge ensured?

Cleaning of drain pipe and

collector reservoir.

External condensation pump or

floater defective.

Is the catch pan full of water and

the pump is not working?

Have pump replaced by certified

service center.

Non-discharged condensation is in

the condensation line.

Is the condensation line routed

downward or not plugged?

Route the condensation line

downward or clean it.

Condensation cannot be

discharged.

Are the condensation lines clear

and routed downward? Does the

condensation pump and the floater

switch work?

Route the condensation line

downward or clean it. If the floater

switch or the condensation pump is

defective, have them replaced.

Functional problem

REMKO ATY

16