Set up inside a building
■
Make sure there is sufficient
heat discharge, if the exterior
unit is set up in the basement,
the attic, in secondary rooms or
hallways (Fig. 7).
■
Install an additional fan with
the same air volume flow as
the exterior unit installed in the
room, which can compensate
for any possible additional
pressure losses through air
channels (Fig. 7).
■
Ensure a continuing unimpaired
air supply from outside, if
possible through opposite,
sufficiently large air openings
(Fig. 7)
.
Minimum clearances
The minimum clearances are to
be provided for maintenance and
repair work and for optimum air
distribution.
ATY 260 AT
ATY 350 AT
A
100 mm
100 mm
B
700 mm
700 mm
C
400 mm
400 mm
D
100 mm
100 mm
E
300 mm
300 mm
■
Observe the static and
other construction technical
regulations and conditions
regarding the building and,
if necessary, provide sound
insulation.
Minimum clearances
E
C
B
A
D
1000
1000
1000
1000
Air inlet
Air
discharge
Warm air
Cold
fresh air
Light well
Exterior unit
Warm air
Light well
Additional fan
7 Set up inside the building
300
REMKO ATY
20