beautypg.com

Confi guring alarms – Orion System GPC-XP Controller User Manual

Page 39

background image

Section 10: Confi guring Alarms

GPC-XP Controller Technical Guide

39

Confi guring Alarms

Alarm Notifi cation

The GPC-XP can generate alarms for remote alarm notifi cation if
alarms have been enabled and Prism 2 is connected and running 24
hours a day. If an alarm condition occurs, the

button in

the upper right hand corner of the GPC-XP Controller Status Screen
will light up. See Figure 80 below. If no alarm(s) exists, the button
will be gray. See

Figure 81

below

.

Figure 81: No Alarms Button

Individual alarms will also be indicated with a bright red alarm bell
icon in the Analog Inputs Status, Binary Inputs Status, and Relays
Status Windows
. See Figure 82 below.

Figure 82: Analog Inputs Status, Binary Inputs
Status, and Relay Status Alarm Icon

Alarm

Indicator

Alarm

Indicator

Alarm

Indicator

Confi guring and Enabling Alarms

Alarms are confi gured and enabled in the Analog Inputs Confi gu-
ration Window
(Figure 11, page 13), Binary Inputs Confi guration
Window
(Figure 26, page 18), and Relay Confi guration Screen
(Figure 34, page 21).

Alarms are also enabled in the GPC-XP Alarms Window.

To

confi gure alarms, click on the

or

button

in the upper right hand corner of the GPC-XP Controller Status
Screen
(Figure 8, page 11). The GPC-XP Alarms Window will
open. See Figure 83.

Figure 80: ALARM Button

Figure 83: GPC-XP Alarms Window

Click the Enabled box beside any Alarm you wish to enable. When
that alarm condition occurs, the

button in the upper right

corner of the Main Prism Screen will turn bright red (Figure 80,
page 39 &
Figure 6, page 10). This selection will also allow that
Alarm to send out an email notifi cation if your system is set up for
that function. See the Prism 2 Technical Guide for instructions on
setting up email alarm notifi cations.

Due to the quantity of Inputs and Outputs on the GPC-XP, alarms
have been grouped into ”Sensor Input High/Low Alarm Indication”
and “Relay Run Time Alarm Indication.”

The remaining 3 alarm indicators apply strictly to Lead/Lag Relay
operations. The Proof Source Failure indicator isn’t limited to fl ow
monitoring. It applies to any type of proof of operation your Lead/
Lag requires whether it is Temperature, CFM - Airfl ow, PPM – Parts
Per Million content, etc.

If the proof source doesn’t meet the requirements in the programmed
amount of time, the system switches to the standby output and gener-
ates the proof alarm and either the Lead or Standby alarm, depending
on which relay caused the condition.

If either or both Lead/Lag Relays generate an alarm, normal operation
can be restored by clicking the

< Reset Lead/Lag>

button. Clicking

the

button will restart the system using the relay

with the least amount of accumulated run time. Both do not have
to be in an alarm state for you to reset the lead/lag operation. If the
system has switched to the standby output, it can be restored to the
lead output if you want to test it again or repairs have been made
and you just want to restore normal operations.

If both outputs generate an alarm, they will not attempt to activate
again until the

button has been clicked. This is

to protect the equipment from possible severe damage if an output
is attempting to operate damaged equipment.