beautypg.com

ONICON System-10 Dualnet User Manual

Page 7

background image

11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]
System-10 Dual Network Interface Installation Guide 05/14 - 0972-1

Page

7

1.5 NETWORK SIGNAL CONNECTIONS

1.5.1 RS485

Use 18 – 22 twisted shielded cable for RS485, 2-wire (half-duplex) serial

communications. The cable is connected to terminal T1A. Do not exceed 4.4 in-lb (0.5

Nm) of torque when tightening the terminals.

CAUTION

Only qualified service personnel should make connections between the System-10 BTU Meter

and the user’s external equipment. ONICON assumes no responsibility for damage caused to

the external equipment as a result of an improper installation.

!

Terminal

T1A

G terminal only used
for 3-wire installations.
Do not connect shields
to this terminal.

CAUTION

Incoming and outgoing RS485 cable shield wires should be connected together, but must not be

connected to the Btu meter.

!