REGISTER
ADDRESS
DESCRIPTION
REGISTER TYPE
READ/
WRITE
COMMENT
41035
Energy Total Mode 1 –Btu
Floating point register (1 of 2)
Read Only
41036
Energy Total Mode 1 –Btu
Floating point register (2 of 2)
Read Only
41037
Energy Total Mode 2 –Btu
Floating point register (1 of 2)
Read Only
41038
Energy Total Mode 2 –Btu
Floating point register (2 of 2)
Read Only
41039
Energy Total Mode 1 – TonHr
Floating point register (1 of 2)
Read Only
41040
Energy Total Mode 1 – TonHr
Floating point register (2 of 2)
Read Only
41041
Energy Total Mode 2 – TonHr
Floating point register (1 of 2)
Read Only
41042
Energy Total Mode 2 – TonHr
Floating point register (2 of 2)
Read Only
41043
Energy Total Mode 1 – kWHr
Floating point register (1 of 2)
Read Only
41044
Energy Total Mode 1 – kWHr
Floating point register (2 of 2)
Read Only
41045
Energy Total Mode 2 – kWHr
Floating point register (1 of 2)
Read Only
41046
Energy Total Mode 2 – kWHr
Floating point register (2 of 2)
Read Only
41047
Volume Total Mode 1 –Gal
Floating point register (1 of 2)
Read Only
41048
Volume Total Mode 1 –Gal
Floating point register (2 of 2)
Read Only
41049
Volume Total Mode 2 –Gal
Floating point register (1 of 2)
Read Only
41050
Volume Total Mode 2 –Gal
Floating point register (2 of 2)
Read Only
41051
Volume Total Mode 1 – Liters
Floating point register (1 of 2)
Read Only
41052
Volume Total Mode 1 – Liters
Floating point register (2 of 2)
Read Only
41053
Volume Total Mode 2 – Liters
Floating point register (1 of 2)
Read Only
41054
Volume Total Mode 2 – Liters
Floating point register (2 of 2)
Read Only
41055
Volume Total Mode 1 – M³
Floating point register (1 of 2)
Read Only
41056
Volume Total Mode 1 – M³
Floating point register (2 of 2)
Read Only
41057
Volume Total Mode 2 – M³
Floating point register (1 of 2)
Read Only
41058
Volume Total Mode 2 – M³
Floating point register (2 of 2)
Read Only
41079
Volume Total Mode 1 – Ft³
Floating point register (1 of 2)
Read Only
41080
Volume Total Mode 1 – Ft³
Floating point register (2 of 2)
Read Only
41081
Volume Total Mode 2 – Ft³
Floating point register (1 of 2)
Read Only
41082
Volume Total Mode 2 – Ft³
Floating point register (2 of 2)
Read Only
41059
Mass Total –Lbs
Floating point register (1 of 2)
Read Only
Mass units are only
available when using
F-2000 Vortex meter
41060
Mass Total –Lbs
Floating point register (2 of 2)
Read Only
41061
Mass Total –kg
Floating point register (1 of 2)
Read Only
41062
Mass Total –kg
Floating point register (2 of 2)
Read Only
41063
Auxiliary Input Total (Di3)
Floating point register (1 of 2)
Read Only
41064
Auxiliary Input Total
Floating point register (2 of 2)
Read Only
REGISTER
ADDRESS
DESCRIPTION
REGISTER
TYPE
DATA
RANGE
OVER
RANGE
READ/
WRITE
COMMENT
41065
Zero Mode 1 Energy Total
0 – 1
0 – 1
N/A
Read/Write
Write a value of 1 to
registers to reset totals.
Re-write a value of zero
to the register once the
totals reset.
41066
Zero Mode 1 Volume Total
0 – 1
0 – 1
N/A
Read/Write
41067
Zero Mode 2 Energy Total
0 – 1
0 – 1
N/A
Read/Write
41068
Zero Mode 2 Volume Total
0 – 1
0 – 1
N/A
Read/Write
41069
Zero Auxiliary Input Total (Di3)
0 – 1
0 – 1
N/A
Read/Write