System-10 Dual Network Interface Installation Guide 05/14 - 0972-1
Page
21
REGISTER
ADDRESS
DESCRIPTION
REGISTER
TYPE
DATA
RANGE
OVER
RANGE
READ/
WRITE
COMMENT
41001
Meter Operating Mode
Indicator
Integer
1 – 3
Not
applicable
Read Only
1 – indicates single mode
2 – indicates dual mode
3 – indicates bi-directional
mode
41002
Mode Status Indicator
Integer
1 – 2
Not
applicable
Read Only
1 - indicates heating mode
or forward direction
2 - indicates cooling mode
or reverse direction
REGISTER
ADDRESS
DESCRIPTION
REGISTER TYPE
READ/
WRITE
COMMENT
41003
Energy Rate – Btu/Hr
Floating point register (1 of 2)
Read Only
41004
Energy Rate – Btu/Hr
Floating point register (2 of 2)
Read Only
41005
Energy Rate – kW
Floating point register (1 of 2)
Read Only
41006
Energy Rate – kW
Floating point register (2 of 2)
Read Only
41007
Energy Rate – Tons
Floating point register (1 of 2)
Read Only
41008
Energy Rate – Tons
Floating point register (2 of 2)
Read Only
41009
Volume Rate – GPM
Floating point register (1 of 2)
Read Only
41010
Volume Rate – GPM
Floating point register (2 of 2)
Read Only
41011
Volume Rate – GPH
Floating point register (1 of 2)
Read Only
41012
Volume Rate – GPH
Floating point register (2 of 2)
Read Only
41013
Volume Rate – MGD
Floating point register (1 of 2)
Read Only
41014
Volume Rate – MGD
Floating point register (2 of 2)
Read Only
41015
Volume Rate – L/S
Floating point register (1 of 2)
Read Only
41016
Volume Rate – L/S
Floating point register (2 of 2)
Read Only
41017
Volume Rate – L/M
Floating point register (1 of 2)
Read Only
41018
Volume Rate – L/M
Floating point register (2 of 2)
Read Only
41019
Volume Rate – L/H
Floating point register (1 of 2)
Read Only
41020
Volume Rate – L/H
Floating point register (2 of 2)
Read Only
41021
Volume Rate – M³/Hr
Floating point register (1 of 2)
Read Only
41022
Volume Rate – M³/Hr
Floating point register (2 of 2)
Read Only
41071
Volume Rate - Ft
3
/S
Floating point register (1 of 2)
Read Only
41072
Volume Rate - Ft
3
/S
Floating point register (2 of 2)
Read Only
41073
Volume Rate - Ft
3
/M
Floating point register (1 of 2)
Read Only
41074
Volume Rate - Ft
3
/M
Floating point register (2 of 2)
Read Only
41023
Mass Rate – Lb/Hr
Floating point register (1 of 2)
Read Only
Mass units are only
available when using
an F-2000 Series
Vortex meter
41024
Mass Rate – Lb/Hr
Floating point register (2 of 2)
Read Only
41025
Mass Rate – Kg/Hr
Floating point register (1 of 2)
Read Only
41026
Mass Rate – Kg/Hr
Floating point register (2 of 2)
Read Only
41027
Supply Temperature – °F
Floating point register (1 of 2)
Read Only
41028
Supply Temperature – °F
Floating point register (2 of 2)
Read Only
41029
Return Temperature – °F
Floating point register (1 of 2)
Read Only
41030
Return Temperature – °F
Floating point register (2 of 2)
Read Only
41031
Supply Temperature – °C
Floating point register (1 of 2)
Read Only
41032
Supply Temperature – °C
Floating point register (2 of 2)
Read Only
41033
Return Temperature – °C
Floating point register (1 of 2)
Read Only
41034
Return Temperature – °C
Floating point register (2 of 2)
Read Only