beautypg.com

ONICON System-10 Dualnet User Manual

Page 14

background image

11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]
System-10 Dual Network Interface Installation Guide 05/14 - 0972-1

Page

14

STEP

ACTION

REACTION

COMMENT

0

Obtain device address &

device instance number from

the network administrator.

None.

The device address is a three

digit number from 001 – 127.

The device instance number can

be anything from 0 – 4,194,303.

1

With the meter running, open

the front panel, locate and

momentarily press the

pushbutton switch DEV ADD /

PROG ENAB.

None.

DEV ADD / PROG ENAB is

located in the lower left corner

of the System-10 processor board

next to the DB9 connector (See

appendix page A-1).

2

Momentarily press the

PROGRAM pushbutton on the

front panel of the display. If

this is not done, the display

will revert to the RUN mode

after 5 minutes.

The System-10 will change to the

PROGRAM mode. The top line of

the LCD will indicate PPPPPPPP.

The second line will read DEVICE

ID and the first digit of the 3 digit

MAC address will be blinking.

The PROGRAM pushbutton is

on the front panel.

3

Successively press the SCROLL

pushbutton to increment the

number to the desired value

from 0 – 9.

The blinking number

increments by one each

time you press the SCROLL

pushbutton.

The SCROLL pushbutton is on

the front panel.

4

Momentarily press the

RESET pushbutton once.

The second digit will now be

blinking.

The RESET pushbutton is on the

front panel.

5

Successively press the SCROLL

pushbutton to increment the

number to the desired value

from 0 – 9.

The blinking number increments

by one each time you press the

SCROLL pushbutton.

The SCROLL pushbutton is on

the front panel.

6

Momentarily press the RESET

pushbutton once.

The third digit will now be

blinking.

The RESET pushbutton is on the

front panel.

7

Successively press the SCROLL

pushbutton to increment the

number to the desired value

from 0 – 9.

The blinking number

increments by one each

time you press the SCROLL

pushbutton.

The SCROLL pushbutton is on

the front panel.

8

Once the correct address is

displayed, momentarily press

the PROGRAM pushbutton.

The INSTNCE page is now

displayed with the first digit of the

device instance number blinking.

The PROGRAM pushbutton is

on the front panel.

9

Use the SCROLL pushbutton

and RESET pushbutton as

described above to enter the

new device instance number.

Each digit will increment and the

RESET pushbutton will advance the

blinking cursor to the next digit.

The SCROLL pushbutton and

the RESET pushbutton are on

the front panel.

10

Once the correct address is

displayed, momentarily press

the PROGRAM pushbutton.

The FM LOCN page appears with

UNKNWN defaulted as the current

location.

The PROGRAM button is on the

front panel.

11

Press the SCROLL button.

The setting will toggle between

UNKNOWN, SUPPLY, and

RETURN.

Refer to Section 4.5 of the

System-10 Installation and

Operation Guide if you wish to

change the settings.

12

Press the PROGRAM button.

The FRONT PANEL RESET page

appears.

It is not necessary to change

anything on this page.

13

Momentarily press the

PROGRAM pushbutton.

The SAVE CHANGES page appears. The new addresses must be

saved to take effect.

14

Momentarily press the SCROLL

pushbutton.

The “N” changes to “Y” on the

SAVE CHANGES page.

The “Y” must be selected in order

for the new addresses to take effect.

15

Momentarily press the

PROGRAM pushbutton.

The new addresses are saved and the

display will revert to the RUN mode.