ONICON System-10 Dualnet User Manual
Page 24
11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]
System-10 Dual Network Interface Installation Guide 05/14 - 0972-1
Page
24
REGISTER
ADDRESS
DESCRIPTION
REGISTER
RANGE
DATA
RANGE
OVER
RANGE
READ/
WRITE
COMMENT
40032
Energy Total Mode 1 – TonHr
0 – 65535
0 – 999
Read Only
Low Order
40033
Energy Total Mode 1 – kTonHr
0 – 65535
0 – 65534
65535
Read Only
High Order
40034
Energy Total Mode 2 – TonHr
0 – 65535
0 – 999
Read Only
Low Order
40035
Energy Total Mode 2 – kTonHr
0 – 65535
0 – 65534
65535
Read Only
High Order
40036
Energy Total Mode 1 – kWHr
0 – 65535
0 – 999
Read Only
Low Order
40037
Energy Total Mode 1 – MWHr
0 – 65535
0 – 999
Read Only
Middle Order
40038
Energy Total Mode 1 – GWHr
0 – 65535
0 – 65534
65535
Read Only
High Order
40039
Energy Total Mode 2 – kWHr
0 – 65535
0 – 999
Read Only
Low Order
40040
Energy Total Mode 2 – MWHr
0 – 65535
0 – 999
Read Only
Middle Order
40041
Energy Total Mode 2 – GWHr
0 – 65535
0 – 65534
65535
Read Only
High Order
40042
Volume Total Mode 1 - kGal
0 – 65535
0 – 999
Read Only
Low Order
40043
Volume Total Mode 1 - MGal
0 – 65535
0 – 999
Read Only
Middle Order
40044
Volume Total Mode 1 – GGal
0 – 65535
0 – 65534
65535
Read Only
High Order
40045
Volume Total Mode 2 – kGal
0 – 65535
0 – 999
Read Only
Low Order
40046
Volume Total Mode 2 – MGal
0 – 65535
0 – 999
Read Only
Middle Order
40047
Volume Total Mode 2 – GGal
0 – 65535
0 – 65534
65535
Read Only
High Order
40048
Volume Total Mode 1 – kLiters
0 – 65535
0 – 999
Read Only
Low Order
40049
Volume Total Mode 1 – MLi-
ters
0 – 65535
0 – 999
Read Only
Middle Order
40050
Volume Total Mode 1 – GLiters
0 – 65535
0 – 65534
65535
Read Only
High Order
40051
Volume Total Mode 2 – kLiters
0 – 65535
0 – 999
Read Only
Low Order
40052
Volume Total Mode 2 – MLi-
ters
0 – 65535
0 – 999
Read Only
Middle Order
40053
Volume Total Mode 2 – GLiters
0 – 65535
0 – 65534
65535
Read Only
High Order
40054
Volume Total Mode 1 –M³
0 – 65535
0 – 999
Read Only
Low Order
40055
Volume Total Mode 1 – kM³
0 – 65535
0 – 65534
65535
Read Only
High Order
40056
Volume Total Mode 2 –M³
0 – 65535
0 – 999
Read Only
Low Order
40057
Volume Total Mode 2 – kM³
0 – 65535
0 – 65534
65535
Read Only
High Order
40058
Mass Total – kLbs
0 – 65535
0 – 999
Read Only
Mass units are only
available when using
F-2000 Vortex Meter.
40059
Mass Total – MLbs
0 – 65535
0 – 65534
65535
Read Only
40060
Mass Total – Kkgs
0 – 65535
0 – 999
Read Only
40061
Mass Total – Mkgs
0 – 65535
0 – 65534
65535
Read Only
40062
Auxiliary Input Total (Di3)
0 – 65535
0 – 999
Read Only
Low Order
40063
Auxiliary Input Total (x1000)
0 – 65535
0 – 65534
65535
Read Only
High Order
40064
Zero Mode 1 Energy Total
0 – 1
0 – 1
N/A
Read/Write
Write a value of 1 to
registers to reset totals.
Re-write a value of
zero to registers once
the totals reset.
40065
Zero Mode 1 Volume Total
0 – 1
0 – 1
N/A
Read/Write
40066
Zero Mode 2 Energy Total
0 – 1
0 – 1
N/A
Read/Write
40067
Zero Mode 2 Volume Total
0 – 1
0 – 1
N/A
Read/Write
40068
Zero Auxiliary Input Total (Di3)
0 – 1
0 – 1
N/A
Read/Write