1.4 PROTOCOL SELECTION
The System-10 Dual Network BTU Meter is provided with an IP connection and a single RS485
connection. Both MODBUS TCP/IP and BACnet UDP/IP are always available from the IP
connection via a single IPv4 IP address. The RS485 connection can be configured for BACnet
MS/TP or MODBUS RTU. The protocol options are selected via dip switch settings. The table
below identifies the dip switch settings for each protocol. The switch settings also control
which network is allowed to remotely reset totals on the network.
Dip switch SW3 Protocol selection and reset function settings
Protocols
Reset
1
2
3
4
BACnet IP/Modbus TCP/Modbus RTU
None
Off
Off
Off
Off
BACnet IP/Modbus TCP/Modbus RTU
BACnet IP
On
Off
Off
Off
BACnet IP/Modbus TCP/Modbus RTU
Modbus TCP
Off
On
Off
Off
BACnet IP/Modbus TCP/Modbus RTU
Modbus RTU
On
On
Off
Off
BACnet IP/Modbus TCP/BACnet MSTP
None
Off
Off
On
Off
BACnet IP/Modbus TCP/BACnet MSTP
BACnet IP
On
Off
On
Off
BACnet IP/Modbus TCP/BACnet MSTP
Modbus TCP
Off
On
On
Off
BACnet IP/Modbus TCP/BACnet MSTP
BACnet MS/TP
On
On
On
Off
Baud Rate Dip
Switches
(See Section 1.6.1)
Protocol Selection
Switches