ONICON System-10 Dualnet User Manual
Page 23
11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]
System-10 Dual Network Interface Installation Guide 05/14 - 0972-1
Page
23
Integer Registers
REGISTER
ADDRESS
DESCRIPTION
REGISTER
RANGE
DATA
RANGE
OVER
RANGE
READ/
WRITE
COMMENT
40001
Meter Operating Mode
Indicator
1 – 3
Not
applicable
Read Only
1 – indicates single mode
2 – indicates dual mode
3 – indicates bi-directional
mode
40002
Mode Status Indicator
1 – 2
Not
applicable
Read Only
1 - indicates heating mode
or forward direction
2 - indicates cooling mode
or reverse direction
40003
Energy Rate – Btu/Hr
0 – 65535
0 - 65534
65535
Read Only
40004
Energy Rate – kBtu/Hr
0 – 65535
0 - 65534
65535
Read Only
40005
Energy Rate – MBtu/Hr
0 – 65535
0 - 65534
65535
Read Only
40006
Energy Rate – kW
0 – 65535
0 - 65534
65535
Read Only
40007
Energy Rate – kW x 10
0 – 65535
0 - 65534
65535
Read Only
40008
Energy Rate – Tons
0 – 65535
0 - 65534
65535
Read Only
40009
Volume Rate – GPM
0 – 65535
0 – 65534
65535
Read Only
40010
Volume Rate – GPM x 10
0 – 65535
0 – 65534
65535
Read Only
40011
Volume Rate – GPH
0 – 65535
0 – 65534
65535
Read Only
40012
Volume Rate – MGD
0 – 65535
0 – 65534
65535
Read Only
40013
Volume Rate – L/S
0 – 65535
0 – 65534
65535
Read Only
40014
Volume Rate – L/M
0 – 65535
0 – 65534
65535
Read Only
40015
Volume Rate – L/Hr
0 – 65535
0 – 65534
65535
Read Only
40016
Volume Rate – M³/Hr
0 – 65535
0 – 65534
65535
Read Only
40017
Volume Rate – M³/Hr x 10
0 – 65535
0 – 65534
65535
Read Only
40018
Mass Rate – Lb/Hr
0 – 65535
0 – 65534
65535
Read Only
Mass units are only
available when using
F-2500 Vortex Meter.
40019
Mass Rate – Lb/Hr x 10
0 – 65535
0 – 65534
65535
Read Only
40020
Mass Rate – kg/Hr
0 – 65535
0 – 65534
65535
Read Only
40021
Mass Rate – kg/Hr x 10
0 – 65535
0 – 65534
65535
Read Only
40022
Supply Temperature – °F
0 – 65535
0 - 655.35
Not
applicable
Read Only
Multiply by 0.01 to read
temperature to 2 decimal
places.
40023
Return Temperature – °F
0 – 65535
0 - 655.35
Not
applicable
Read Only
40024
Supply Temperature – °C
-32768
to
+32767
-327.68
to
+327.67
Not
applicable
Read Only
40025
Return Temperature – °C
-32768
to
+32767
-327.68
to
+327.67
Not
applicable
Read Only
40026
Energy Total Mode 1 - kBtu
0 – 65535
0 – 999
Read Only
Low Order
40027
Energy Total Mode 1 - MBtu
0 – 65535
0 – 999
Read Only
Middle Order
40028
Energy Total Mode 1 – GBtu
0 – 65535
0 – 65534
65535
Read Only
High Order
40029
Energy Total Mode 2 – kBtu
0 – 65535
0 – 999
Read Only
Low Order
40030
Energy Total Mode 2 – MBtu
0 – 65535
0 – 999
Read Only
Middle Order
40031
Energy Total Mode 2 – GBtu
0 – 65535
0 – 65534
65535
Read Only
High Order