beautypg.com

ONICON System-10 Dualnet User Manual

Page 15

background image

11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]
System-10 Dual Network Interface Installation Guide 05/14 - 0972-1

Page

15

1.7.2 Changing the IP Address, Subnet mask and Gateway Address

Changing the IP address requires a PC with an Ethernet card and an available port. The

network interface is accessed using a web browser such as Internet Explorer. Both the PC

and the Btu meter must be configured to operate on the same IP network. Assuming the Btu

meter is programmed with the default address of 192.168.1.24, configure the PC to operate

with an IP address of 192.168.1.1 and a subnet mask of 255.255.255.0. Follow the procedure

outlined below to edit the IP address, subnet mask and gateway address.

1. Connect an RJ45 Ethernet cable between the PC and the System-10 and power the

Btu meter. Allow 60 seconds for the display firmware to cycle through start-up

diagnostic routines.

2. Open Internet Explorer and enter an address of http://192.168.1.24.

3. From navigation tree on the right in the image below, select setup and then network

settings.

4. Enter the new IP address, subnet mask and gateway address as needed. Click

on Update IP Settings to update the settings and then click on System Restart to

complete the update.

Navigation Tree

System restart required
to complete the update.