beautypg.com

ONICON System-10 Dualnet User Manual

Page 18

background image

11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]
System-10 Dual Network Interface Installation Guide 05/14 - 0972-1

Page

18

2.2 BAC OBJECTS

The System-10 BTU Meter operates in one of three operating modes: single, dual or bi-

directional. The table below contains point information for each of the operating modes.

In single mode operation, only one register accumulates energy and one register accumulates

volume. Thus, only two AV points and two BV reset points are necessary.

BACNET OBJECT

OBJECT DESCRIPTION

UNITS

NOTES

Analog Input 1

Energy Rate

Btu/Hr, kW or Tons

Analog Input 2

Volume Rate

L/Sec, L/Min, L/Hr,

M

3

/Hr, GPM, CFS or

CFM

Analog Input 3

Supply Temperature

Degrees C or F

Analog Input 4

Return Temperature

Degrees C or F

Analog Value 1

Mode 1 Energy Total

Btu, TonHrs or kWHrs

Analog Value 2

Mode 1 Volume Total

Liters, M

3

, Gallons or Ft

3

Analog Value 3

Mode 2 Energy Total

Btu, TonHrs or kWHrs

Only used in dual-mode

applications.

Analog Value 4

Mode 2 Volume Total

Liters, M

3

or Gallons

Only used in dual-mode

applications.

Analog Value 5

Auxiliary Input Total

(Di3)

None

BACnet will not report

engineering units for this

object.

Analog Value 6

Operating Mode

(Single, Dual or

Bi-directional)

Not Applicable

None = 0

Single = 1

Dual = 2

BiDir = 3

Analog Value 12

Mode 1 Mode 2

Indication

Not Applicable

Mode 1 = 1

Mode 2 = 2

Binary Value 11

Zero Mode 1 Energy Total

Not Applicable

Changing this property from
the (0) inactive state to the
(1) active state will reset
the total to zero. (Must be
priority 8 manual operator).

Binary Value 12

Zero Mode 1 Volume Total Not Applicable

Binary Value 13

Zero Mode 2 Energy Total

Not Applicable

Binary Value 14

Zero Mode 2 Volume Total Not Applicable

Binary Value 15

Zero Auxiliary Input Total

Not Applicable