System-10 Dual Network Interface Installation Guide 05/14 - 0972-1

Page

5

1.3 SPECIFICATIONS

RS485 (BACnet MS/TP or MODBUS RTU)

Transceiver: 2-wire, half-duplex

Baud rate: 9600, 19200, 38400 & 76800

Termination: 120 ohms or none (Default: none)

Biasing: None

Flow control: None

BACnet UDP/IP & MODBUS TCP/IP

Transceiver: 10Base T, 10Mbps, Rj45 connection

Default IP address: 192.168.1.24

Default Subnet Mask: 255.255.255.0

BACnet Port: 47808

MODBUS Port: 502

Flow control: None

Address Ranges

MODBUS device address range: 1 – 127 (Default: 017)

BACnet device address range: 1 – 127 (Default: 017)

BACnet Device Instance range: 0 - 4,194,303 (Default: 57017)

SECTION 1: INTRODUCTION

1.1 PURPOSE OF THIS GUIDE

The purpose of this guide is to provide installation and commissioning procedures and basic

operating and servicing instructions for the ONICON System-10 Dual Network BTU Meter

Network Interface.

1.2 TYPICAL SYSTEM-10 BTU METER

ONICON’S System-10 is a true heat (Btu) computer which accepts data from several sensors,

performs a series of computations with that data, and displays and/or transmits the results as an

indication of the amount of heat (Btu’s) being transferred per unit time or as a totalized amount.

SYSTEM-10

RETURN

SCROLL

RESET

PROGRAM

BTU METER

ONICON

3864

FLOW DIRECTION

SUPPLY

24, 120 or 120 VAC

Input Power

Individual Chiller

or Boiler

System

Mains

Local display of flow, temperature and

energy data

RETURN

TEMP

SENSOR

SUPPLY

TEMP

SENSOR

BACnet and/or MODBUS

COMMUNICATIONS

TO NETWORK

ONICON insertion

flow meter purchased

separately