F-4000 Series Ultrasonic Flow Meter Manual 05/15 - 0707-13 / 18838
Page 43
Holding Registers (Read Only)
Description
Address
Register Type
Bytes
Data Type
Example
Aeration
1015
Holding Register
4
Real
0.0
Average Flow
1003
Holding Register
4
Real
89.657
Delta Time
1011
Holding Register
4
Real
191.114
Liquid Flow
1001
Holding Register
4
Real
89.723
Liquid Total
1007
Holding Register
4
Real
5436.23
Raw Flow
1005
Holding Register
4
Real
1587.675
Signal Strength
1013
Holding Register
4
Real
73.0
Sonic Velocity
1009
Holding Register
4
Real
1495.36
Input Registers (Read Only)
Description
Address
Register Type
Bytes
Data Type
Example
Alarm Status
107
Input Register
2
Integer
28
Day
103
Input Register
2
Integer
13
Flow Velocity
1001
Input Register
4
Real
29.165
Highest Expected Flow
1005
Input Register
4
Real
260.368
Hour
104
Input Register
4
Integer
16
Lowest Expected Flow
1007
Input Register
4
Real
-260.368
Minute
105
Input Register
2
Integer
13
Month
102
Input Register
2
Integer
7
Second
106
Input Register
2
Integer
47
Signal
1003
Input Register
4
Real
195.1
Year
101
Input Register
2
Integer
32 (+1980)
Coil Status
Description
Address
Register Type
Bytes
Data Type
Example
Reset Totalizer
1
Coil
1
Boolean
0
Discreet Input (Read Only)
Description
Address
Register Type
Bytes
Data Type
Example
Aeration
5
Input Register
1
Boolean
1
Empty
2
Input Register
1
Boolean
1
Fault
4
Input Register
1
Boolean
1
Interface
8
Input Register
1
Boolean
1
Makeup
7
Input Register
1
Boolean
1
Memory
6
Input Register
1
Boolean
1
Pig
9
Input Register
1
Boolean
1
Rate
3
Input Register
1
Boolean
1
Spacing
1
Input Register
1
Boolean
1
Zeromatic
10
Input Register
1
Boolean
1