ONICON F-4000 Series User Manual
Page 39
11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • [email protected]
F-4000 Series Ultrasonic Flow Meter Manual 05/15 - 0707-13 / 18838
Page 39
5.3 BACnet
DEVICE OBJECT
Property
Description and/or Example
Object _ Identifier
Instance number (1- 4,194,303)
Set via front panel user interface
Object _ Name
Writeable (15 characters max) Default: ONICON
Object _ Type
Device (8)
System _ Status
OPERATIONAL (0)
Vendor _ Name
ONICON Inc.
Vendor _ Identifier
206
Model _ Name
F-4000
Firmware _ Revision
2.04.06 (or later)
Application _ Software _ Version
012813-1338
Protocol _ Version
1
Protocol _ Revision
10
Protocol _ Services _ Supported
Read property, read property multiple, write property
Protocol _ Object _ Types _ Supported
Device, Analog Value, Binary Value
Object _ List
Dx, AV0…AV28, BV0…BV10
Max _ APDU _ Length _ Supported
480
Segmentation _ Supported
No _ Segmentation (3)
Local _ Time
HH:MM:SS
Local _ Date
MM:DD:YY
APDU _ Timeout
0
Number _ Of _ APDU _ Retries
0
Device _ Address _ Binding
0
Database _ Revision
2
ANALOG VALUE OBJECT List
BACnet Object
Object _ Name
BACnet Object
Object _ Name
AV0
Flow
AV15
Highest expected flow
AV1
Average flow
AV16
Lowest expected flow
AV2
Raw flow
AV17
Aeration alarm level
AV3
Volume total
AV18
Slew mode selection
AV4
Sonic velocity
AV19
Time averaging period
AV5
Delta time
AV20
Smart slew seed
AV6
Valc
AV21
Device status
AV7
Aeration
AV22
Site name
AV8
Deadband control
AV23
Version information
AV9
Batch/sample total
AV24
Date/time last reset
AV10
High flow alarm level
AV25
Op sys P/N
AV11
Low flow alarm level
AV26
Firmware checksum
AV12
Vs alarm level
AV27
Compile time info
AV13
Flow velocity
AV28
System date/time
AV14
Signal