ONICON F-4000 Series User Manual
Page 31
11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • [email protected]
F-4000 Series Ultrasonic Flow Meter Manual 05/15 - 0707-13 / 18838
Page 31
4.3 INSTALLING RECALLED SITES
When you “Install” a site, you activate the transducers so the meter can read flow. During this process,
the meter will select the best operating frequency and establish baseline operating parameters such as
the speed of sound reading in meters/second.
There are two different procedures for installing a site. One procedure is for transducers mounted in the
reflect mode on steel or copper pipe. The other is for transducers mounted in the direct mode. The two
procedures are detailed below.
4.3.1 Reflect Mount Installations
Follow the specific instructions below to complete the installation of the meter in reflect mount
mode. If your meter is installed in direct mount mode, advance to section 4.2.2.
If at any time you wish to return to the beginning of this procedure, press
repeatedly until
you arrive at Step#1.
Step
Press the Following
Keypad Pushbutton
Displayed Information
(After Keypress)
Comment
1.
2.
3.
4.
(Press 3 times)
5.
Your transducer model and size may be different.
Consult the Site Installation Details form for the
exact series and size.
6.
(Press 3 times)
7.
8.
9.
Display will cycle through drives as the initial
installation is completed. Wait for this to complete.
It is possible that the meter will display a message other than the speed of sound. Section 6 in this manual
describes these messages and how to resolve them. Please contact ONICON with questions or concerns.