F-4000 Series Ultrasonic Flow Meter Manual 05/15 - 0707-13 / 18838
Page 42
o
Point-To-Point, modem, (Clause 10), baud rate(s):
o
LonTalk, (Clause 11), medium:
o
BACnet/ZigBee (ANNEX O)
o
Other:
Device Address Binding:
Is static device binding supported? o Yes þ No
Networking Options:
o
Router, Clause 6 - List all routing configurations, e.g., ARCNET-Ethernet, Ethernet- MS/TP, etc.
o
Annex H, BACnet Tunneling Router over IP
5.4
Modbus
Modbus is a commonly used protocol for communication in supervisory and data acquisition
(SCADA) applications. It uses registers to address data which can be formatted in various types
including, REAL, INTEGER, & BOOLEAN (coils).
The following Modbus Function Codes are supported:
Function Code
Name
Description
1
Read Coil(s)
Read one or more coil present values (0 or 1)
2
Read Discreet Input(s)
Read one or more discreet input present values (0 or 1)
3
Read Holding Register(s)
Read one or more holding register present values
4
Read Input Register(s)
Read one or more input register present values
5
Write Single Coil
Write (0 or 1) to a single coil
6
Write Single Register
Write to a single holding register
15
Write Multiple Coils
Write (0 or 1) to multiple coils
16
Write Multiple Registers
Write to a multiple holding registers
Memory Map
Alarm Status Input Register (Read Only)
Description
Address
Register Type
Bytes
Data Type
Example
Alarm Status
295
Input Register
16
String
__ERF___
Data Entry Holding Registers (Read & Write)
Description
Address
Register Type
Bytes
Data Type
Example
Aeration Alarm Level
1115
Holding Register
2
Integer
50
Batch Sample Total
1107
Holding Register
4
Real
10.0
Deadband Control
1105
Holding Register
4
Real
0.0
Hi Flow Alarm Level
1109
Holding Register
4
Real
100.0
Lo Flow Alarm Level
1111
Holding Register
4
Real
10.0
Slew Mode Selection
1101
Holding Register
2
Real
1
Smart Slew
1104
Holding Register
2
Integer
6
Time Average
1102
Holding Register
4
Real
10.0
Vs Alarm Level
1113
Holding Register
4
Real
2100.0