ONICON F-4000 Series User Manual
Page 33
11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • [email protected]
F-4000 Series Ultrasonic Flow Meter Manual 05/15 - 0707-13 / 18838
Page 33
4.3.2 Direct Mount installations
Follow the specific instructions below to complete the installation of the meter in direct
mount mode.
If at any time you wish to return to the beginning of this procedure, press
repeatedly
until you arrive at Step#1.
Step
Press the Following
Keypad Pushbutton
Displayed Information
(After Keypress)
Comment
1.
2.
3.
4.
(Press 3 times)
5.
Your transducer model and size may be different.
Consult the Site Installation Details form for the exact
series and size.
6.
(Press 3 times)
7.
8.
9.
Display will cycle through drives as the initial
installation is completed. Wait for this to complete.
It is possible that the meter will display a message other than the speed of sound. Section 6 in this manual
describes these messages and how to resolve them. Please contact ONICON with questions or concerns.
10.
None
Displays the measured speed of sound. This number
should closely approximate the speed of sound
listed on the Site Installation Details document.
Complete the following steps only if flow can be stopped in the pipe. If not, skip to the last step in this table.
11.
MTYmatic is the default empty pipe detection
setting.
12.
13.
Enter Zero Flow Adjust. Use Up/Down keys as
necessary to select Actual Zero.