ANALOG VALUE OBJECT Properties
Property Identifier
Description and/or Example
R/W
Object_Identifier
Unique identifier number
R
Object_Type
2 – Analog Value
R
Present_Value
Real (Floating point) Number
R
Description
Character string representing engineering units (e.g. GAL/MIN)
R
Units
No-units (95)
R
Status_Flags
IN_ALARM,FAULT,OVERRIDDEN,OUT_OF_SERVICE (e.g. 0,0,0,0)
R
Event_State
0 - NORMAL
R
Out_Of_Service
0 - FALSE
R
BINARY VALUE OBJECTS
BACnet Object
Description
BV0
Totalizer reset (Read/Write)
BV1
Spacing alarm (Read only)
BV2
Empty alarm (Read only)
BV3
Rate alarm(Read only)
BV4
Fault alarm (Read only)
BV5
Aeration alarm (Read only)
BV6
Memory alarm (Read only)
BV7
Makeup alarm (Read only)
BV8
Interface alarm (Read only)
BV9
Pig alarm (Read only)
BV10
Zeromatic alarm (Read only)
BINARY VALUE OBJECT Properties
Property Identifier Description and/or Example
R/W
Object_Identifier
Unique identifier number
R
Object_Type
5 – Binary Value
R
Present_Value
Binary (e.g. 0 or 1)
R/W*
Description
Character string representing object function (e.g. Aeration Alarm)
R
Priority_Array
Manual Operator (8)
R
Status_Flags
IN_ALARM,FAULT,OVERRIDDEN,OUT_OF_SERVICE (e.g. 0,0,0,0)
R
Event_State
NORMAL
R
Out_Of_Service
FALSE
R