16 | Web Interface
Table 5: Basic Parameters
Basic Parameter
Description
Source
Configures the humidifier to either accept analog control signals from a
humidistat or digital signals from a Building Management System.
Control channels
Configures the humidifier to either operate with a single channel (control
only) or dual channel (control and high limit).
Channel 1 type
Configures the Volt or amp range of the control signal connected to Channel 1.
Can be used to configure the humidifier to be On/Off. However, Nortec
recommends using the Security Loop for On/Off applications.
Control mode
Configures the type of control used with the humidifier. RH (P) is
proportional only internal control based on a transducer signal. RH (PI) is
proportional control with an integral.
Channel 2 type
Configures the Volt or amp range of the control signal connected to Channel 2.
Can be used to configure the humidifier to be On/Off. However, Nortec
recommends using the Security Loop for On/Off applications.
Multi mode
Use Multi Mode to configure the humidifier to operate as one humidifier of
a group controlled by a single control signal / transducer signal. (Default =
Standalone)
Zero output
System demand at which the humidifier should shut off (Default = 0%)
Full output
System demand at which the humidifier should output its full capacity
(Default = 100%).
Allow remote disable
Temporarily disables the humidifier from operating.
Table 6: Multi Unit Parameters
Multi unit Parameter
Description
Multi mode
Use Multi Mode to configure the humidifier to operate as one humidifier of a
group controlled by a single control signal / transducer signal. (Default =
Standalone)
Zero output
System demand at which the humidifier should shut off (Default = 0%)
Full output
System demand at which the humidifier should output its full capacity
(Default = 100%).
Table 7: Unit control Parameters
Unit control Parameter Description
Allow remote disable
Temporarily disables the humidifier from operating.