beautypg.com

Nortec HumDigital User Manual

Page 9

background image

Created: 04.06.2007

9

Changed: 21.12.2007
Printed: 02.03.2009

The advanced status display (STAT) or the settings (SETT) for the selected
zone can be selected using the softkeys below the display.

2.1.2 Status menu (STAT)

The status menu shows the status in detail. As well as the relative humidity,
temperature and the status there is also additional information on the zone.
This shows whether the zone is ready for operation (zone ready) or which
problem has occurred in case of malfunction.

Parameter

Name

Function

Notes

Hum:

Current humidity [% RH], sensor resolution 0.1 %
RH

Temp:

current temperature [°C] or [°F], resolution 0.1 °C

Stat:

Summary of status

Info:

Additional status information

Status

Display

Priority*

Description

ERR

1 Error

Hand

2 Manual operation on

Humid

3 Humidification active

FWA

4 AFWS active

H req

5 Humidification request

AFWS req

6 AFWS request

Stdby

7 Standby (e.g. target value reached)

* When two status reports occur at once, that with lower priority is shown.

Info

Display

Priority*

Description

Com err

1 Communication error with HumiPur

Cap err

2 Capability error: HumiPur cannot fulfil the function required.

Causes: Firmware not updated, device technology outdated

no HPS

3 No HPS entered.

Sens err

4 Communication with sensor disturbed (e.g. sensor malfunction)

Max err

5 Maximum hygrostat released

HPS err

6 HPS not released (timeout)

Unkn err

7 Unknown error

Zone Ready

8 Zone ready for operation

* When two status reports occur at once, that with lower priority is shown.