Parameters for CSF3200 (PER)
Name
Function
Notes
Dtype:
Device type
CSF3200 (M261,M262, M263,
D250)
DNum:
Device number
(D251,D252)
Con:
Conductivity
µ
S (D240)
Press:
Pump pressure
bar (D239)
Flow rate:
Flow rate
L/h (D238)
Stat:
Summary of status
See table below
Info:
Additional status information
See table below
Status of CSF3200 (PER)
Display
Priority*
Description
ERR
1 Error (M200, M201, M204, M236, M237, M253), com error
Full
2 Tank full (M239)
ON
3 In operation
* When two status reports occur at once, that with lower priority is shown.
Info on CSF3200 (PER)
Display
Priority*
Description
Com err
1 Communication error
Cap err M
2 Capability error: CenterPur cannot fulfil the function required.
Causes: Firmware not updated, device technology outdated
Cap err D
3 Capability error: PER cannot fulfil the function required.
Causes: Firmware not updated, device technology outdated
Safety press. err
7 Safety pressure error (M201)
Inlet press. err
8 Inlet pressure error (M200)
Conductivity err
3 Conductivity error (M236)
Motor prot. err
6 Motor protection error (M253)
Pump press. err
5 Pump pressure error (M237)
Mntc pump
9 Pump maintenance (M204)
PerPur ready
10 PER ready for operation
* When two status reports occur at once, that with lower priority is shown.
Parameters for LS3400 (SYN)
Name
Function
Notes
Dtype:
Device type
LS3400 (M261,M262, M263,
D250)
DNum:
Device number
(D251,D252)
Con:
Conductivity
µS (D248)
Stat:
Summary of status
See table below
Info:
Additional status information
See table below