beautypg.com

Nortec HumDigital User Manual

Page 13

background image

Created: 04.06.2007

13

Changed: 21.12.2007
Printed: 02.03.2009

2.2.2 Status menu


Select a unit with the UP/DOWN keys and display the detailed status with the
“STAT” softkey.

## STATUS HIG #1 d

Dtype: HPS3200
DNum: 4294967296
Stat: ON

Info: HighPur ready


Parameters for CSF3121 (PER)

Name

Function

Notes

Dtype:

Device type

CSF3121 (M261,M262, M263, D250)

DNum:

Device number

(D250,D251)

Stat:

Summary of status

See table below

Info:

Additional status information

See table below

Status of CSF3121 (PER)

Display

Priority*

Description

ERR

1 Error (M201, M236, M250, M251), com error

Full

2 Tank full (M235)

ON

3 In operation

* When two status reports occur at once, that with lower priority is shown.

Info on CSF3121 (PER)

Display

Priority*

Description

Com err

1 Communication error

Cap err

2 Capability error: CSF cannot fulfil the function required.

Causes: Firmware not updated, device technology outdated

Safety press. err

3 Safety pressure error (M201)

Inlet press. err

5 Inlet pressure error (M236)

Conductivity err

6 Conductivity error (M250)

Motor prot. err

4 Motor protection error (M251)

PerPur ready

7 PER ready for operation

* When two status reports occur at once, that with lower priority is shown.