Nortec HumDigital User Manual

Page 23

background image

Created: 04.06.2007

23

Changed: 21.12.2007
Printed: 02.03.2009

The parameters transferred can only be read; it is not possible to change the
settings via the BMS.


3.1.2 Telegram


Every five seconds, the HumCenter sends a telegram with the parameters
described above. The following is an explanation of the symbols used in the
telegram and the telegram layout, using an example.

The following symbols are used in the telegram:

Symbol

Description

Notes

*

Start symbol

Start of telegram

A

– Z

Identifier

Identifies the parameter

:

Index

Index in case of array data (D:1)

;

Data separator

Separates the data (D:1; 25.0; 50.0

– “;”

separates the data from the index and
the temperature from the humidity)

.

Decimal point

CR+LF

End of line

Lines of telegram finish with a “carriage
return” and “line feed”.



Layout of a sample telegram with the following configuration:

- 3 zones (HumSpots)
- 2 containers


Telegram:

*A07;11;2007;11;29;04;B0C2D:1;43.3;24.8;D:2;42.5;23.3;D3:40.8;20.1Z3221
9

The telegram contains the following information:

- Date/time: 07.11.2007, 11:29:04 (A07;11;2007;11;29;04)

- Zone alarms: No alarm (B0)

- Container alarms: Container 2 alarm (C2)

- Zone 1 values: Humidity: 43.3 % rH, temp.: 24.8 °C

(D:1;43.3;24.8)

- Zone 2 values: Humidity: 42.5 % rH, temp.: 23.3 °C

(D:1;42.5;23.3)