Installation – Desa VSGF36NRA User Manual

Page 16

background image

www.desatech.com

116746-01A

16

CHECKING GAS CONNECTIONS

WARNING: Test all gas pip-

ing and connections, internal

and external to unit, for leaks

after installing or servicing. Cor-

rect all leaks at once.

WARNING: Never use an

open flame to check for a leak.

Apply a noncorrosive leak

detection fluid to all joints.

Bubbles forming show a leak.

Correct all leaks at once.

CAUTION: Make sure exter-

nal regulator has been installed

between propane/LP supply and

fireplace. See guidelines under

Connecting Fireplace to Gas

Supply, page 15.

PRESSURE TESTING GAS SUPPLY
PIPING SYSTEM
Test Pressures In Excess Of 1/2 PSIG
(3.5 kPa)
1. Disconnect fireplace with its main gas valve

(control valve) and equipment shutoff valve

from gas supply piping system. Pressures

in excess of 1/2 psig will damage fireplace

regulator.

2. Cap off open end of gas pipe where equipment

shutoff valve was connected.

3. Pressurize supply piping system by either

opening propane/LP supply tank valve for

propane/LP gas or opening main gas valve

located on or near gas meter for natural gas

or using compressed air.

4. Check all joints of gas supply piping system.

Apply noncorrosive leak detection fluid to all

joints. Bubbles forming show a leak.

5. Correct all leaks at once.
6. Reconnect fireplace and equipment shutoff

valve to gas supply. Check reconnected fittings

for leaks.

Test Pressures Equal To or Less Than
1/2 PSIG (3.5 kPa)
1. Close equipment shutoff valve (see Figure 18).

INSTALLATION

Continued

Figure 18 - Equipment Shutoff Valve

Open

Closed

Equipment
Shutoff Valve

Figure 20 - Checking Gas Joints for

Propane/LP Gas

Propane/LP
Supply Tank

Equipment
Shutoff
Valve

Gas Control Valve

Gas Meter

Figure 19 - Checking Gas Joints for

Natural Gas

Gas Control Valve

Equipment Shutoff Valve

2. Pressurize supply piping system by either

opening propane/LP supply tank valve for

propane/LP gas or opening main gas valve

located on or near gas meter for natural gas

or using compressed air.

3. Check all joints from gas meter to equipment

shutoff valve for natural gas or propane/LP

supply to equipment shutoff valve for propane/

LP (see Figures 19 and 20). Apply noncorro-

sive leak detection fluid to all joints. Bubbles

forming show a leak.

4. Correct all leaks at once.

PRESSURE TESTING FIREPLACE GAS
CONNECTIONS
1. Open equipment shutoff valve (see Figure 18).
2. Open main gas valve located on or near gas

meter for natural gas or open propane/LP

supply tank valve.

3. Make sure control knob of fireplace is in the

OFF position.