INSTALLATION

Continued

WARNING: Never connect

natural gas fireplace to private

(non-utility) gas wells. This

gas is commonly known as

wellhead gas.

Installation Items Needed
Before installing fireplace, make sure you have

the items listed below.
• external regulator for propane/LP unit only

(supplied by installer)

• piping (check local codes)
• sealant (resistant to propane/LP gas)
• equipment shutoff valve *
• test gauge connection *
• sediment trap (optional)
• tee joint
• pipe wrench
• approved flexible gas line with gas connector

(if allowed by local codes) (not provided)

* A CSA design-certified equipment shutoff valve

with 1/8" NPT tap is an acceptable alternative to

test gauge connection. Purchase the optional CSA

design-certified equipment shutoff valve from your

dealer. See Accessories, page 31.
For propane/LP units, the installer must supply

an external regulator. The external regulator will

reduce incoming gas pressure. You must reduce

incoming gas pressure to between 11 and 14 inches

of water. If you do not reduce incoming gas pres-

sure, heater regulator damage could occur. Install

external regulator with the vent pointing down

as shown in Figure 14. Pointing the vent down

protects it from freezing rain or sleet.

* Purchase the optional CSA design-certified

equipment shutoff valve from your dealer. See

Accessories, page 31.
** Minimum inlet pressure for purpose of input

adjustment.

Figure 15 - Gas Connection

Sediment Trap

CSA Design-Certified
Equipment Shutoff Valve
With 1/8" NPT Tap*

3" Minimum

Cap Pipe Tee

Nipple Joint

Natural Gas
From Gas Meter
(5" W.C.** to 10.5"
W.C. Pressure)
Propane/LP
From External
Regulator
(11" W.C.** to 14"
W.C. Pressure)

CAUTION: Use only new,

black iron or steel pipe. Inter-

nally-tinned copper tubing may

be used in certain areas. Check

your local codes. Use pipe of

1/2" diameter or greater to allow

proper gas volume to fireplace.

If pipe is too small, undue loss

of volume will occur.

Installation must include an equipment shutoff

valve, union and plugged 1/8" NPT tap. Locate

NPT tap within reach for test gauge hook up.

NPT tap must be upstream from fireplace (see

Figure 15).
IMPORTANT:

Install equipment shutoff valve

in an accessible location. The equipment shutoff

valve is for turning on or shutting off the gas to

the appliance.
Check your building codes for any special re-

quirements for locating equipment shutoff valve

to fireplaces.
Apply pipe joint sealant lightly to male NPT

threads. This will prevent excess sealant from

going into pipe. Excess sealant in pipe could result

in clogged fireplace valves. Never use sealant on

flare threads.

Propane/LP
Supply Tank

External
Regulator

Figure 14 - External Regulator With Vent

Pointing Down

Vent
Pointing
Down