Installation – Montigo H42DF User Manual

Page 16

background image

H*42DF Indoor Gas Fireplace

Page 16

XG0148 - 150204.1

Installation

Figure 15. Rear Vent Venting Graph for wall mounted terminations.

Notes Wall Mounted Terminations: REAR VENT

„

All dimension lengths for vertical or horizontal runs are measured

from center of the vent pipe.

„

Venting runs must fall within the limits set by the venting graphs,

see Figure 15.

„

Fireplace must be converted to Rear Vent configuration prior to

running vent, see Figure 9 and 9a.

The Venting Graph
Measure the vertical height from the fireplace hearth to the centre of the

termination and the horizontal run from the fireplace flue collar to the wall

flange of the termination. Plot on the Venting Graph Figure 15 with an 'X'.
If the 'X' falls on or above the top boundary of the shaded area, the

installation is acceptable.
Example A: (Acceptable Installation)

If the vertical dimension from the hearth is 120" and the horizontal

run to the wall flange of the vent termination is 138", this would be

an acceptable installation.

Example B: (Unacceptable Installation)

If the vertical dimension from the hearth is 48" and the horizontal

run to the wall flange of the vent termination is 96",this would NOT

be an acceptable installation.

Example C: (Unacceptable Installation)

If the vertical dimension from the floor of the fireplace is 72" and

the horizontal run to the wall flange of the vent termination is 120",
this would NOT be an acceptable installation.

Figure 15b. Rear Vented, wall mounted Multi-elbow termination installation.

Installation for H*42DF* must have a minimum vertical rise of 52".The vent run

must comply with the Venting Graph for Rear vent, wall mounted terminations,

Figure 15.

Figure 15a. Straight run, Rear Vented, wall mounted termination for H*42DF*,

Figure 15. N.G. (Natural Gas) equipped fireplaces ONLY. For Propane

fireplaces, see figure 15b below.

NOTE: 18” MAX. horizontal run

with no vertical lift. N.G. (Natural

Gas) fireplaces ONLY.

PXT Extension

RHS101 Heat

Shield

Termination

Hearth

Exterior

Wall

18” MAX.

33"

6”

30” Max.

52” Min.

18”

Max.

Flex or Rigid

Section

19”

Min.

33”

6”

33”

18” NG Only

A

B

C

52”

48”

Unacceptable vent run

within shaded area.

Acceptable vent run

within non-shaded area.

If your installation does not fall

within the venting graph parameters,

please contact a local Montigo

dealer for Power Venting options.

Note: Images are shown without screens for clarity purposes. However,

your fireplace should not be operated without proper installation of

screens.