24-Port PoE Injector User’s Manual

Page 24/40

Port Power Limit: Displays the power limit to a single port.
Start Condition: Displays the type of start condition.
Power Management Mode: There are 5 modes for selecting, please refer to the

table below.

And then, click

Apply

Power Management Mode interface

Management Mode:

Dynamic - based on actual power used (mode 1).

Static - preset by user (mode 2 & 3)

Class - set classification by PD, also according to IEEE 802.3af (mode 4 & 5).

Total Allocated Power:

Consumption - sum of power consumed by all ports.

Class - sum of all ports power according to their class, except for class 0 & 4 for

which the actual power consumption is summed.


Port Power Limit:

Predefined - user defined limit by port power limit.

Class - if PD’s power exceeds power according to its class.

Max - full power according to 802.3af (15.4W, 44V)

Start Condition:

N/A - no special condition.

Class - start port only, if its maximum allowed power according to its class is higher

than the user defined power limit; except for classes 0-4 for which no

start condition exists.

[Note]

PD class 1 power is 4w, PD class 2 power is 7w, PD class 0, 3, 4 power is 15.4w.