beautypg.com

Ch 5 - discrete output modules, Pointscan/142, Overview – Measurement Computing PointScan 100 Series rev.1.0 User Manual

Page 23: Wiring, Tpo feature, I/o registers, 5 - discrete output modules, High density discrete output, Module, Discrete output modules 5

background image

PointScan/100 User’s Manual

8-28-01

Discrete Output Modules 5-1

Discrete Output Modules

5

This section documents the following module

PointScan/142

PointScan/142

High Density Discrete Output Module

Overview

Sixteen discrete output channels each provide up to 1 Amp DC to motor contactors, valves, and other loads.
Inductive surge protection is provided. Each of the sixteen outputs may optionally be configured as Time
Proportioned Outputs that pulse ON at a duty cycle proportional to an analog output register value.
Typically these TPO outputs are controlled by a PID loop or other process algorithm in a control program.
More information can be found in the on-line help supplied with the IO Toolkit program.

Number of Channels

16 discrete outputs connected to a common DC source

Output Voltage Range

10 - 30 VDC

Max. Load per Output

1 Amp

Max. Load per Module

8 Amps

Max. Inrush Current

5 Amps (for 100 mS)

Wiring

A single terminal is provided for each output channel. All outputs are powered from the DC power
terminal. All channels are referenced to a common return, which is connected to the negative side (ground)
of the DC power source.

TPO Feature

Time proportioned outputs pulse ON and OFF with a duty cycle proportional to an analog value stored in
an analog output register. TPO outputs are a low cost way to get smooth proportional control of heaters and
other process variables. Typically, TPO analog output registers are assigned to the output of PID or other
control program. Use the IO Toolkit to set pulse cycling as fast as 10 mS or as slow (many minutes) as your
system dynamics require. Each output may be configured as a TPO or ordinary discrete output.

I/O Registers

Function

IOtech Registers

Modbus Registers

Discrete Outputs

Y0 – Y15

00001 – 00016

TPO Values

AY0 – AY15

40001 – 40016