beautypg.com

Ch 4 - discrete i/o modules, Pointscan/129, Overview – Measurement Computing PointScan 100 Series rev.1.0 User Manual

Page 19: Wiring and jumpers, Tpo feature, 4 - discrete i/o modules, 8 discrete inputs and, 8 discrete outputs, Overview -1 wiring and jumpers -1 tpo feature -1, Discrete i/o modules 4

background image

PointScan/100 User’s Manual

9-12-01

Discrete I/O Modules 4-1

Discrete I/O Modules

4

This section documents the following modules

PointScan/129, PointScan/122, PointScan/127

PointScan/129

8 Discrete Inputs and 8 Discrete Outputs

Overview

This module provides one terminal for each input or output channel. All inputs may be wired as sourcing or
sinking. Outputs are wired in a sourcing (power switching) configuration only. An input count feature uses
analog input registers to accumulate the positive transitions of each input. More information can be found
in the on-line help in the IO Toolkit program.

Number of Channels

8 discrete inputs, 8 discrete outputs (PointScan/129 only)

Input Voltage Range

12/24 VDC/VAC

Input Current @ 24 VDC

6.7 mA

Output Voltage Range

10 – 30 VDC

Maximum Count Rate

100 Hz (6000 / minute) each input, plus selectable 2KHz (120,000 /
minute) mode for input 1 only

Wiring and Jumpers

One wire from each sourcing field input should be bussed together and connected to terminal
17 (DC +). One wire from each sourcing field output and/or or sinking field input should be bussed
together and connected to terminal 18 (DC GND). Refer to the wiring diagram below. Set jumper W1 to
match the wiring configuration of the inputs.

TPO Feature

Time proportioned outputs pulse ON and OFF with a duty cycle proportional to an analog value stored in
an analog output register. TPO outputs are a low cost way to get smooth proportional control of heaters and
other process variables. Typically, TPO analog output registers are assigned to the output of PID or other
control program. Use the IO Toolkit to set pulse cycling as fast as
10 mS or as slow (many minutes) as your system dynamics require. Each output may be configured as a
TPO or ordinary discrete output. I/O Registers

Function

IOtech Registers

Modbus Registers

Discrete Inputs

X0 – X7

10001 – 10008

Discrete Outputs

Y0 – Y7

00001 – 00008

TPO Values

AY0 – AY7

40001 – 40008

Counter Inputs

AX0 – AX7

30001 – 30008