beautypg.com

Pointscan/127, Overview, Input wiring – Measurement Computing PointScan 100 Series rev.1.0 User Manual

Page 21: I/o registers, High speed counter, Module, Overview -3 input wiring -3 i/o registers -3

background image

PointScan/100 User’s Manual

9-12-01

Discrete I/O Modules 4-3

PointScan/127

High Speed Counter Module

Overview

This high-speed counter module has eight isolated circuits that accept pulse inputs from a variety of
sources, including quadrature and incremental encoders. Count values are reported in 16 bit analog input
registers or 32 bit long registers. The states of the counter inputs are also reported as discrete inputs. Pulse
rates up to 50 kHz are supported. The counters can be reset by toggling discrete output bits. Counter modes
are selected using the IO Toolkit program. More information on this and other features can be found in the
on-line help supplied with the IO Toolkit program.

Number of Channels

8 discrete inputs, isolated

Input Voltage Range

12/24 VDC/VAC

Input Current @ 24 VDC

6.7 mA

Input Wiring

Screw terminal assignments are shown below. For best noise immunity, connect input signals using twisted
wire pairs. To maintain the best differential noise rejection, do not connect
(-) screw terminals together at the I/O base. Positive DC voltage must be applied to an input to indicate an
ON condition. Refer to the wiring diagram below.

Any odd-numbered input can be gated by connecting a gating signal to the next highest even-numbered
input. For example, Input 2 can gate the counter for Input 1.

I/O Registers

Function

IOtech Registers

Modbus Registers

Discrete Inputs

X0 – X7

10001 – 10008

Counter Inputs

AX0 – AX7 or LI0 – LI7

30001 – 30008
35001 – 35008

Resets

Y0 – Y7

00001 – 00008