Measurement Computing CIO-DAS08-AOH User Manual
Page 16

The register's Write layout is :
BASE + 3 (Read / Write) Write Functions
R0
R1
R2
R3
X
X
X
X
BIT 0
BIT 1
BIT 2
BIT 3
BIT 4
BIT 5
BIT 6
BIT 7
The register's Read layout is :
BASE + 3 (Read / Write) Read Functions
R0
R1
R2
R3
MA0
MA1
MA2
X
BIT 0
BIT 1
BIT 2
BIT 3
BIT 4
BIT 5
BIT 6
BIT 7
R3 to R0: Indicate the current analog input range.
MA2 to MA0: Indicate the analog input channel that is currently selected (by writing to base +2).
6.4.1CIO-DAS08-AOH GAIN/RANGES
The gain/range of the board is controlled by writing a control code to the Base + 3 register. The gain/range codes are:
0
1
1
0
6
6
+/-0.005
1000
0
1
1
1
E
14
+/-0.01
500
0
0
1
0
4
4
+/-0.05
100
0
0
1
1
C
12
+/-0.1
50
0
1
0
0
2
2
+/-0.5
10
0
1
0
1
A
10
+/-1
5
0
0
0
0
0
0
+/-5
1
0
0
0
1
8
8
+/-10
0.5
R0
R1
R2
R3
HEX
DEC
RANGE V
GAIN
CONTROL CODES
BI-POLAR AOH
1
1
1
0
7
7
0 to 0.01
1000
1
0
1
0
5
5
0 to 0.1
100
1
1
0
0
3
3
0 to 1
10
1
0
0
0
1
1
0 to 10
1
R0
R1
R2
R3
HEX
DEC
RANGE V
GAIN
CONTROL CODES
UNI-POLAR AOH
6.4.2 CIO-DAS08-AOL GAIN/RANGES
There are fewer ranges available for the CIO-DAS08-AOL. Gains of 2, 4 & 8 are often called binary gains. These
ranges are not available on the MetraByte DAS-8AO. The gain/range of the board is controlled by writing a control code
to the Base + 3 register.
0
1
1
0
6
6
+/-0.625
8
0
0
1
0
4
4
+/-1.25
4
0
1
0
0
2
2
+/-2.5
2
0
0
0
0
0
0
+/-5
1
0
0
0
1
8
8
+/-10
0.5
R0
R1
R2
R3
HEX
DEC
RANGE V
GAIN
CONTROL CODES
BI-POLAR AOL
12