Infloor Infloorboard User Manual
Page 10

www.Infloor.com
10
DESIGN & PERFORMANCE
Thermalboard 250' Loops 20¡F Temp Drop*
BTU/SQ/FT
10.00
15.00
20.00
25.00
30.00
35.00
40.00
Friction Loss (Ft. Head)
2.22
4.70
8.01
12.10
16.96
22.80
28.87
Water Speed (Ft./Second)
0.60
0.90
1.20
1.50
1.80
2.10
2.40
GPM Per Loop
0.18
0.27
0.36
0.45
0.54
0.63
0.72
Thermalboard 200' Loops 20¡F Temp Drop
BTU/SQ/FT
10.00
15.00
20.00
25.00
30.00
35.00
40.00
Friction Loss (Ft. Head)
0.98
2.07
3.53
5.33
7.47
9.93
12.72
Water Speed (Ft./Second)
0.45
0.68
0.90
1.13
1.35
1.58
1.80
GPM Per Loop
0.14
0.20
0.27
0.34
0.41
0.47
0.54
*Shaded areas have high head loss
DESIGNER’S NOTE
Remember average water temperature means the average of the supply and
return water temperatures flowing to and from the loop. Most typically
Infloorboard™ is designed with a 20F° temperature drop. This means the sup-
ply water temperature would typically be 10F° higher than the average water
temperature.
INFLOORBOARD™ 250’ LOOPS 20°F TEMP DROP•
INFLOORBOARD™ 200 LOOPS 20°F TEMP DROP