Function
The thermostatic regulating unit is designed for maintaining the
temperature set for the flow fluid constant in a low temperature
circuit for underfloor radiant panels.
This unit has been specially designed for use with both the external
and wall embedded versions of
the separator/distribution
manifolds.
It comes supplied with a three-way thermostatic mixing valve with
built-in temperature sensor, a three-speed pump, a safety
thermostat, a differential by-pass valve, flow and return temperature
gauges and secondary circuit shut-off valves.
Supplied complete with preformed insulation shell.
Product range
Part # 31093 External thermostatic regulating unit for radiant panels for Sepcoll. Flow upwards, flow on right hand side
Size 1 ”
Part # 31094 External thermostatic regulating unit for radiant panels for Sepcoll. Flow upwards, flow on left hand side
Size 1”
cert. n° 0003
ISO 9001
Technical specification
Three-way thermostatic valve
Materials: - Body:
brass EN 1982 CB753S
- Internal cartridge
chemically nickel plated
- Springs:
stainless steel
- Seals:
EPDM
By-pass
Materials: - Body:
brass EN 1982 CB753S
- Springs:
stainless steel
- Obturator:
EPDM
- Seals:
EPDM
Shut-off valves
Materials: - Body:
brass EN 12165 CW617N
- Seals:
EPDM
Performance
Medium:
water, glycol solutions
Max. percentage of glycol:
30%
Setting temperature range:
25 – 55°C
Accuracy:
± 2°C
Primary inlet max. temperature:
85°C
By-pass setting range:
10-60 kPa (1- 6 m w.g.)
Connections: - primary circuit:
1” F with union
- secondary circuit:
1” F
- connection centre distance:
90 mm
Safety thermostat
Wiring diagrams
Set temperature:
55°C
Protection class:
IP 55
Contacts rating:
10 A/ 240 V
brass EN 12164 CW614N,
L
N
230 V
Ambient
thermostat
Safety
thermostat
5
4
3
2
1
0
3
2,5
2
1,5
1
0,5
0
H (m w.g.)
G (m
3
/h)
3
2
1
0,40
0,30
0,20
90
65
45
1800
1100
700
I
(A)
(W)
(r.p.m.)
P
n
Speed
UPS 25-60
2
1
3
Head available at the regulating
unit connections
Power consumption
Pump
0
6
/
5
2
S
P
U
:
p
m
u
p
d
e
e
p
s
-
e
e
r
h
T
Material: - Body:
GG 15/20 cast iron
Electric supply:
230 V - 50 Hz
Max. relative humidity:
95%
Max. ambient temperature:
80°C
Protection class:
IP 44
Pump centre distance:
Pump connections:
1 1/2” with union
130 mm