beautypg.com

Infloor Brass Manifold User Manual

Infloor Radiators

background image

Pre-assembled distribution manifolds

for radiant panel systems

Function

Distribution manifolds for radiant panel systems are used to

optimally distribute the heating fluid in floor heating system circuits

and ultimately improve the control of heat emission from the panels.

The manifolds ensure that the flow to each circuit is regulated

precisely and also control the shut-off, venting and automatic

removal of air from the system.

Special solutions devised during sizing have also enabled depth to

be reduced and connection between manifold and branches

facilitated.

Technical specification

Materials:

Flow manifold
- body:

brass EN 1982 CB753S

Micrometric balancing valve

- body:

PA

- control device upper part:

brass EN 12164 CW614N

- obturator:

POM

- obturator seal:

EPDM

- knob:

ABS

Return manifold

- body:

brass EN 1982 CB753S

Shut-off valve

- control device upper part:

brass EN 12164 CW614N

and PA

- obturator stem:

stainless steel

- obturator:

EPDM

- springs:

stainless steel

- seals:

EPDM

- knob:

ABS

Ball valve

- body:

brass EN 12165 CW617N

- ball:

brass EN 12164 CW614N, chrome plated

- handle:

aluminium EN AB 46100

End fitting

N

7

1

6

W

C

5

6

1

2

1

N

E

s

s

a

r

b

:

y

d

o

b

-

Automatic air vent valve

- obturator stem:

brass EN 12164 CW614N

- spring:

stainless steel

- seals:

EPDM

- float:

PP

Performance:

Medium:

water, glycol solutions

Max. percentage of glycol:

30%

Max. working pressure:

10 bar

Max. end fitting discharge pressure:

2,5 bar

Working temperature range:

0–80°C

Nr. adjustment curves:

10

Micrometric regulating valve scale:

0–10

Accuracy:

± 5%

Main connections:

1”, 1 1/4” F

Connection centre distance:

195 mm

Outlets:

3/4”M - Ø 18

Outlet centre distance:

50 mm

Product range

Pre-assembled distribution manifold for radiant panel systems

Sizes 1” and 1 1/4”

Reference Documents

Product guides for additional components, such as thermal

actuators, flow meters, pressure differential bypass valves

and darcel fittings.