7

Energy Recovery Ventilator

Cassette slides out*

Access Panels

Access Panels

Exhaust

Side

Outdoor

Air Side

Access Panel

Service Clearances

ERV-10, 20, 45 and 55 units require minimum clearances to perform routine maintenance, such as filter
replacement, energy wheel cassette inspection, and fan belt adjustment. Blower and motor assemblies,
energy recovery wheel cassette and filter sections are always provided with a service door or panel for proper
component access. Clearances for component removal may be greater than the service clearances, refer to
drawings below for these dimensions.

ERV-10, ERV-20, ERV-45, ERV-55

ERV-90, ERV-120

Recommended Service Clearances

Unit Size

R

S

T

X

ERV-10

32

30

42

ERV-20

44

(30 for maintenance)

30

42

ERV-45

60

(39 for maintenance)

40

42

ERV-55

65

(32 for maintenance)

40

42

ERV-90

42

ERV-120

42

All dimensions are in inches.

Arrangement A

T

R

Arrangement A

Cassette

Cassette

Access Panel

Access Panel

Access Panel

Access Panel

X

X

X

X

Cassette

Cassette

Supply
Weatherhood

Exhaust
Weatherhood

Access Panel

Access Panel

Access Panel

Access Panel

Access Panel

Arrangement B, C or D

X

*ERV-10, 20, and 45 only.

X

X

X

S