Energy Recovery Ventilator

Accessing the Energy Recovery Wheel in
Models ERV-90 and 120

Disconnect power to the ERV. Remove access
panel(s) labeled “Energy Wheel Cassette Access”,
which reveals the energy wheel cassette. There are
additional panels that must be removed in order
to slide out the cassettes. (See pictures providing
additional visual information).

Unplug the wheel drive motor and pull the cassette
halfway out as shown.

NOTE: ERV-90 has two energy wheels with access
panels for both wheels. Wheels slide out on opposite
corners.

Energy recovery wheels for ERV-120 are hard-wired
and not designed to slide out.

This panel must
be removed before
the energy wheel
can slide out.
(ERV-90 only)

Removing the Energy Recovery Wheel in
ERV-10

First, remove the drive belts and the collars in both
bearings. On the pulley side of the cassette, remove
the four (4) fasteners that hold the bearing support
channel in place. Once the bearing support is
removed the wheel can be pulled from the cassette.
To replace the wheel, reverse this procedure.

Removing the Energy Recovery Wheel Segments
ERV-20, 45, 55, 90 and 120
(stainless steel rim)

Steel retainers are located on the inside of the wheel
rim. Push the retainer towards the center of the
wheel, then lift up and away to release segments.

Wheel segment removed

Bracket Segment
Retainer

Lift away from
segment

Catch Segment
Retainer

Push toward center

Center of Wheel

Spoke

Inside of wheel rim

IMPORTANT

Place retainers back in the original position before
rotating the energy recovery wheel, otherwise
damage to retainer will occur.