beautypg.com

Optional accessory wiring schematics, Day timer remote panel, Dirty filter indicator – Greenheck ERV (476412) User Manual

Page 14: Unit interfacing terminals, On/off/auto switch & indictor light wiring, Powered by others), Energy recovery ventilator

background image

14

Energy Recovery Ventilator

Optional Accessory Wiring Schematics

W1

12

7

6

Y2

Y1

G

C

R

TERMINAL BLOCKS IN

UNIT CONTROL CENTER

TIMER

BLACK

BLUE

RED

(CAPPED)

7-Day Timer

Remote Panel

The remote panel is available with a number of
different alarm lights and switches to control the unit.
The remote panel ships loose and requires mounting
and wiring in the field. The remote panel is available
with the following options:

• Unit on/off switch

• Unit on/off light

• 7-day time clock

• Hand/off/auto switch

• Dirty filter light

• Economizer light

• Frost control light

• Wheel rotation sensor light

NC

C

NC

C

NO

NO

DIRTY FILTER

EXHAUST DIRTY
FILTER SWITCH

SUPPLY DIRTY
FILTER SWITCH

HOT

COMMON

Dirty Filter Indicator

(powered by others)

A

W1

12

7

6

Y2

Y1

G

C

R

UNIT ON/OFF

COOL STAGE 1 / ECONOMIZER

COOL STAGE 2

UNOCCUPIED RECIRCULATION

S1

S6

S7

S4

S5

HEAT

TERMINAL BLOCKS IN

UNIT CONTROL CENTER

Unit Interfacing Terminals

Heating/Cooling Switches & Night Setback
Switch/Timer

W1

12

7

6

Y2

Y1

G

C

R

NC

C

NC

C

NO

NO

UNIT ON/OFF

FROST CONTROL

ECONOMIZER

WHEEL ROTATION

DIRTY FILTER

ON

OFF

AUTO

*

* -- BMS, TIMECLOCK,

TERMINAL BLOCKS IN

UNIT CONTROL CENTER

ON/OFF/AUTO SWITCH ALLOWS THREE MODES OF OPERATION
"ON" - UNIT IS TURNED ON MANUALLY
"OFF" - UNIT IS TURNED OFF MANUALLY

"AUTO" - UNIT IS CONTROLLED VIA SCHEDULER OF BMS, TIMECLOCK, TSAT, ETC.

TSTAT, RTU, ETC.

EXHAUST DIRTY
FILTER SWITCH

SUPPLY DIRTY
FILTER SWITCH

On/Off/Auto Switch & Indictor Light Wiring