Energy Recovery Ventilator

Variable Frequency Drives

Optional factory installed, wired, and programmed
variable frequency drives (VFDs) may have been
provided for modulating or multi-speed control of the
blowers and energy recovery wheel for economizer
and frost control modes. One VFD, either Yaskawa
model V1000 or J1000, is provided for each blower
(supply air and exhaust) and one Yaskawa model
J1000 is provided for the energy recovery wheel.

Refer to the tables in this section for factory settings
and field wiring requirements. Refer to the unit control
center for unit specific wiring diagram. When making
adjustments outside of the factory set points, refer to
Yaskawa VFD instruction manual, which can be found
online at www.drives.com. For technical support,
contact Yaskawa direct at 1-800-927-5292.

MA MB MC

RP

H1

SC

HC

S7

S6

S5

S4

S3

S2

S1

MP

AC

AM

AC

+V

A2

A1

PC

P2

P1

IG

S-

S+

R-

R+

V1000

MA MB MC

AC

AM

AC

+V

A1

SC

S5

S4

S3

S2

S1

J1000

OPTION 1 - 0-10 VDC CONTROL

SEE VFD INSTALLATION MANUAL FOR MORE DETAIL

USER TO PROVIDE ISOLATION AS REQUIRED

FOR CONTINUOUS 60Hz OPERATION JUMPER TERMINALS A1 AND +V.

WIRED TO A1 (+) AND AC (COMMON)

0-10 VDC CONTROL SIGNAL (BY OTHERS)

10 VDC = 60 Hz

0 VDC = 30 Hz

A1 AC

FOR ONE 0-10 SIGNAL, WIRE TO DRIVES IN PARALLEL

OPTION 2 - MULTI SPEED CONTROL

S5

S4

SC

NEITHER S4 OR S5 CONTACT CLOSED
DRIVE SPEED = 60 Hz.

DRIVE SPEED = 40 Hz.

S4 TO SC CONTACT CLOSED (BY OTHERS)

S5 TO SC CONTACT CLOSED (BY OTHERS)
DRIVE SPEED = 30 Hz.

USER TO PROVIDE CONTACTS AND ISOLATION AS REQUIRED

SEE VFD INSTALLATION MANUAL FOR MORE DETAIL

Frost Control

Timed Exhaust

1. Remove power from unit.

2. Jumper the frost indicating wheel pressure switch

in the unit control center.

3. Jumper the temperature indicating thermodisc in

the unit control center. Thermodisc has a pre-set
temperature of 5ºF.

4. Set the frost control timer scale for T1 and T2 to

1m. Set the timer settings for T1 and T2 to 10.

5. Add power to the unit. Blower

should cycle on for one minute,
then turn off for one minute.

6. Remove power from unit and

remove jumpers that were
placed. Re-set timer settings.

• T1 timer setting set to 5 and

timer scale set to 10m for 5
minutes of wheel off time.

• T2 timer setting set to 5 and

timer scale set to 1h for 30
minutes of wheel on time.

Electric Preheat

1. Remove power from unit.

2. Jumper the frost indicating wheel pressure switch

in the preheat control center.

3. Jumper the temperature indicating thermodisc in

the preheat control center. Thermodisc has a pre-
set temperature of 5º F.

4. Apply power to unit. Preheater should turn on.

Timer
Scale

Timer
Scale

Timer

Settings

T1