Flowserve TRV5-40 User Manual
Page 5
![background image](https://www.manualsdir.com/files/785049/content/doc005.png)
5
Explanatory Notes
– continued –
Description
– continued –
The temperature transmitter TRV 5-40 can be used as:
n
safety temperature monitor / limiter in conjunction with a temperature sensor type TRG 5-6x and
the control unit NRS -40. / NRS -40. and
n
temperature monitor & limiter in conjunction with one or two temperature sensors TRG 5-6x and the
control unit TRS 5-40 or any other equipment that is approved for this application.
The equipment combination can be used for monitoring, limiting or control purposes in steam plants
and (pressurised) hot water installations according to TRD and EN 95 and EN 953.
Function
The temperature transmitter TRV 5-40 consists of the safety part for temperature limiting and the part
for temperature monitoring & control.
The safety part is connected with the temperature sensor. The temperature sensor detects the tem-
perature and sends the measured values to the safety part of the temperature transmitter, where the
measured values are recorded redundantly and monitored.
The adjustable temperature limit T
MAX
(°C), the actual temperature and system malfunctions are
indicated by the temperature transmitter. The temperature sensing element on the electronic insert
monitors continuously the temperature inside the transmitter housing. An automatic self-testing routine
checks every 0 seconds the safety and reliability of the functions of the temperature sensor and the
detection of the measured values.
The actual temperatures, the exceeding of the adjusted temperature limit T
MAX
(°C), the result of the
periodic self test and the temperature inside the transmitter housing are sent as a data telegram via
CAN bus to the control equipment NRS -40. / NRS -40..
Regardless of the safety part two additional temperature sensors TRG 5-6x can be used for tempera-
ture monitoring & control in order to measure further actual temperature values. These readings are
also sent as data telegrams via CAN bus and will be evaluated e. g. by the control unit TRS 5-40.
System components
TRG 5-6x
Temperature sensor with resistance thermometer Pt 00
TRS 5-40
Digital temperature switch
Functions: MIN / MAX temperature monitor and temperature controller
Data exchange: CAN bus to ISO 898 via CANopen protocol
NRS 1-40.1 and NRS 1-40.2
Digital control unit for four sensors (level, temperature)
Functions: Signalling MIN alarm and MAX alarm in freely adjustable combinations
Data exchange: CAN bus to ISO 898 via CANopen protocol
URB 2
Operating & visual display unit
Functions: Parameterisation, visual indication via LCD display
Data exchange: CAN bus to ISO 898, with CANopen protocol