8

Causes

Faulty installation and/or configuration of CAN bus components, excessively high temperatures in

devices, defective electronic component parts or electromagnetic interferences of the supply system

can result in system malfunctions.
Other malfunctions are:

n

Incorrect communication in the CAN bus system

n

Overloading of the 4 V power supply unit that is integrated in the control unit

System Malfunctions

Note

Before carrying out the system malfunction analysis please check:
Wiring:

Is the wiring in accordance with the wiring diagrams?

Is the polarity of the bus lines always correct?

Are the bus lines of the first and the last devices provided with 0 Ω terminating

resistors?
Configuration of the level electrode NRG 1x-40 (Low water level LW):

Are the wire bridges (equipment or ) set correctly?

Does the position of the wire bridge correspond with the node ID setting?
Configuration of the temperature transmitter TRV 5-40:

Is the temperature transmitter TRV 5-40 set correctly as equipment , , 3 or 4?
Node ID:

Are all node ID settings correct?

Note that no node ID setting must be used twice!
Baud rate:

Does the baud rate setting correspond with the cable length?

Is the baud rate setting of all devices identical?