System malfunctions, Fig. 7 – Flowserve TRV5-40 User Manual

Page 20

background image

0

Indication of error code

When an error

occurs

Indication T

Display switches between indication of

error code

(E xx) and actual value T

Error code

Possible cause

Remedy

E.01 ... E.32

Temperature transmitter defective because

a malfunction was detected during one or

more self-testing routines.

Replace temperature transmitter.

E.11

Temperature in transmitter housing too high. Check installation of the temperature

transmitter.

E.12

Resistance in temperature sensor too high.

Check readings of the temperature sensor

(see table “Basic values of measuring

resistors”). Replace measuring element if

the measured values are incorrect.

E.17

Incorrect code switch

G Fig. 3

(Configuration) setting.

Check and correct position of code switches

S 9 and S 0 (polynom).

E.18

Incorrect code switch

G Fig. 3

(Configuration) setting.

Check and correct position of code switches

S to S 8 (limiter number).

E.30

Sensor line interrupted or interruption in

temperature sensor.

Check sensor line and readings of the

temperature sensor (see table “Basic values

of measuring resistors”). If the measured

values are incorrect replace the measuring

element.

E.0b *)

Short circuit in temperature sensor.

Check sensor line and readings of the

temperature sensor (see table “Basic values

of measuring resistor”). If the measured

values are incorrect replace the measuring

element.

*) Do not confuse indication

b and 6!

System Malfunctions

– continued –

Table listing error codes

Fig. 7

Indication of

limit value

Indication of

actual value / error code