System malfunctions, Checking installation and functions – Flowserve TRV5-40 User Manual
Page 21
System Malfunctions
– continued –
Note
The system malfunctions caused by the temperature transmitter TRV 5-40 will also
result in system malfunctions in the control units NRS -40. and NRS -40., which
means that the output contacts open instantaneously and the signal outputs are
energised/de-energised in a pulse-controlled way.
When contacting our Technical Services please state the indicated error code.
Basic values of measuring resistors
°C
0
0
0
30
40
50
60
70
80
90
00
Ω /grd
0
00.00 03.90 07.79 .67 5.54 9.40 3.4 7.07 30.89 34.70 38.50 0.385
00
38.50 4.8 46.06 49.8 53.57 57.3 6.04 64.76 68.47 7.6 75.84 0.373
00
75.84 79.5 83.7 86.8 90.46 94.08 97.70 0.30 04.88 08.46 .03 0.36
300
.03 5.58 9.3 .66 6.8 9.69 33.9 36.67 40.5 43.6 47.06 0.350
400
47.06 50.50 53.93 57.34 60.75 64.4 67.5 70.89 74.5 77.60 80.93 0.338
500
80.93 84.6 87.57 90.87 94.6 97.43 300.70 303.95 307.0 30.43 33.65 0.37
600
33.65 36.86 30.05 33.4 36.4 39.57 33.7 335.86 338.99 34.0 345. 0.35
700
345. 348.30 35.38 354.45 357.5 360.55 363.59 366.6 369.6 37.6 375.6 0.304
800
375.6 378.59 38.55 384.50 387.45 390.38
0.95
Basic values of measuring resistors according to DIN 43760 for Pt 00.
Checking the switchpoints
The switchpoints should be checked during commissioning and whenever the measuring elements of
the temperature sensors or of the temperature transmitter TRV 5-40 are being exchanged.
To check the switchpoint “MAX temperature limit (°C)” the adjusted limit value must be exceeded.
The equipment must then response as if there were an alarm situation.