Basic settings, Commissioning – Flowserve TRV5-40 User Manual

Page 14

background image

4

Basic Settings

Factory settings

The temperature transmitter TRV 5-40 features the following factory set default values:

n

Node ID: 005 for the safety part

n

Baud rate: 50 kBit/s (5 m cable length)

n

Configuration: temperature transmitter TRV 5-40 set as limiter 4.

Commissioning

Checking wiring

Before installation check the wiring:

n

Are the temperature sensors wired according to the wiring diagram?

n

Is the wiring of all CAN bus devices in accordance with the wiring diagrams?

n

Is the polarity of the bus line always correct?

n

Are all the end-of-line devices of the bus line provided with a 0 Ω terminating resistor?

Applying supply voltage

Switch on supply voltage. The two seven-segment indicators are tested, which means that all

segments and decimal points are flashing. The test is also carried out whenever the connector for the

bus line is pulled out of the transmitter and then plugged in again.

Changing system configuration

The control units NRS -40. and NRS -40. associated with the temperature transmitter TRV 5-40

are designed for four limiting functions for monitoring liquid level and temperature. The level electrodes

NRG x-40, NRG x-4. and the temperature transmitter TRV 5-40 are to be connected to the control

unit NRS -40.. The level electrode NRG x-4 and the temperature transmitter TRV 5-40 have to be

connected to the control unit -40..
For the operation of the limiting system it is necessary to establish in the control unit the number of

sensors with which the equipment has to work.
For more information see chapter “Commissioning” in the installation manual NRS -40. and

NRS -40..
The following settings can be adjusted with the TRV 5-40:

n

Communication with control unit NRS -40. or NRS -40.

n

Communication with the control unit operating as limiter , , 3 or 4