MX/QX HART Field Unit FCD LMENIM2340-00 – 1/14
32
Command
Request Data Bytes
Response Data Bytes
No.
Description
Byte
Format
Description
Byte
Format
Description
105
Read Burst
Mode
Configuration
34
0
Unsigned-8
Burst Message
0
1
2
3
4
5
6
7
8
9
10
11
12-13
14-17
18-21
22
23
24
25-28
Unsigned-8
Unsigned-8
Unsigned-8
Unsigned-8
Unsigned-8
Unsigned-8
Unsigned-8
Unsigned-8
Unsigned-8
Unsigned-8
Unsigned-8
Unsigned-8
Unsigned-16
Time
Time
Enum-8
Enum-8
Enum-8
Float
Burst Mode Control Code
31 (0x1F) Command Number Extension Flag
39
Device Variable Code Slot 0
40
Device Variable Code Slot 1
Device Variable Code Slot 2
Device Variable Code Slot 3
Device Variable Code Slot 4
Device Variable Code Slot 5
Device Variable Code Slot 6
Device Variable Code Slot 7
Burst Message
Maximum Number of Burst Messages
Extended Command Number
Update Time (1/32 of a millisecond)
Maximum Update Time (1/32 of a millisecond)
Burst Trigger Mode Code
Device Variable Classification for Trigger Value
Units Code
Trigger Value
106
Flush Delayed
Responses
34
107
Write Burst
Device
Variables
34
0
1
2
3
4
5
6
7
8
Unsigned-8
Unsigned-8
Unsigned-8
Unsigned-8
Unsigned-8
Unsigned-8
Unsigned-8
Unsigned-8
Unsigned-8
Device Variable Code Slot 0
Device Variable Code Slot 1
Device Variable Code Slot 2
Device Variable Code Slot 2
Device Variable Code Slot 4
Device Variable Code Slot 5
Device Variable Code Slot 6
Device Variable Code Slot 7
Burst Message
0
1
2
3
4
5
6
7
8
Unsigned-8
Unsigned-8
Unsigned-8
Unsigned-8
Unsigned-8
Unsigned-8
Unsigned-8
Unsigned-8
Unsigned-8
Device Variable Code Slot 0
40
Device Variable Code Slot 1
Device Variable Code Slot 2
Device Variable Code Slot 2
Device Variable Code Slot 4
Device Variable Code Slot 5
Device Variable Code Slot 6
Device Variable Code Slot 7
Burst Message
108
Write Burst
Mode
Command
Number
34
0-1
2
Unsigned-16
Unsigned-8
Command Number of the response message
to be transmitted
41
Burst Message
0-1
2
Unsigned-16
Unsigned-8
Command Number of the response message to
be transmitted
Burst Message
109
Burst Mode
Control
42
0
1
Unsigned-8
Unsigned-8
Burst Mode Control Code
Burst Message
0
1
Unsigned-8
Unsigned-8
Burst Mode Control Code
Burst Message
115
Read Event
Notification
Summary
43
0
Unsigned-8
Event number = 0
44
0
1
2.7-2.4
2.3-2.0
3-6
7-10
11-14
15-18
19-44
Unsigned-8
Unsigned-8
Bits-4
Enum
Time
Time
Time
Time
Bits
Event Number
Number of events supported
MS 4 Bits of Event Status
LS 4 Bits of Event Notification Control Code
Time when first unacknowledged event was
triggered
45
Event Notification Retry Time
Maximum Update Time
Event De-bounce Interval
Event Mask
46
116
Write Event
Notification Bit
Mask
43
0
1-27
Unsigned-8
Bits
Event Number = 0
44
Event Mask
47
0
1-27
Unsigned-8
Bits
Event Number = 0
Event Mask
117
Write Event
Notification
Timing
43
0
1-4
5-8
9-12
Unsigned-8
Time
Time
Time
Event Number = 0
44
Event Notification Retry Time
Maximum Update Time
48
Event De-bounce Time
0
1-4
5-8
9-12
Unsigned-8
Time
Time
Time
Event Number = 0
Event Notification Retry Time
Maximum Update Time
Event De-bounce Time
118
Event
Notification
Control
43
0
1
Unsigned-8
Unsigned-8
Event Number = 0
44
Event Notification Control Code
0
1
Unsigned-8
Unsigned-8
Event Number = 0
Event Notification Control Code
119
Acknowledge
Event
Notification
43
0
1-4
5-6
7
8-32
Unsigned-8
Time
Unsigned-16
Bits
Bits
Event Number = 0
44
Time when first unacknowledged event was
triggered
Configuration Changed Counter
Device Status
Command 48 Data
0
1-4
5-6
7
8-32
Unsigned-8
Time
Unsigned-16
Bits
Bits
Event Number = 0
Time when first unacknowledged event was
triggered
49
Configuration Changed Counter
Device Status
Command 48 Data
512
Read Country
Code
1-2
3
Unsigned-8
Enum-8
Country Code
50
SI Units Only
513
Write Country
Code
1-2
3
Unsigned-8
Enum-8
Country Code
50
SI Units Only
1-2
3
Unsigned-8
Enum-8
Country Code
50
SI Units Only
5. The Range Values allow the Loop Current to be converted to a percent for use by the actuator (e.g. to use as the actuator setpoint).
6. Issuing this command will write the current Primary Variable value to the Upper Range Value.
7. Issuing this command will write the current Primary Variable value to the Lower Range Value.
8. The Loop Current may not reflect the process while the Self test is executing. A master must not generate spurious error messages or disconnect form the Field Device
while the Self test is in progress.
9. This is equivalent to cycling the power off and then back on to the Field Device. Communication with the network will be temporarily lost. The device will not respond
to subsequent commands until the reset is complete. In addition the Loop Current may not reflect the process while the Device Reset is executing. A master must not
generate spurious error messages or disconnect from the Field Device while the Device Reset is in progress.
10. This trim is typically performed by adjusting the Loop Current to 4.00 milliamperes and sending the measured value to the Field Device. In response the Field Device trims
its calibration of the Loop Current to match the value received from the Master. Response Code 9 “Incorrect Loop Current Mode or Value” will be returned if the device is
not in the proper mode to allow the Loop Current to be calibrated or if the current is not set to exactly the minimum value.